Inspections for the day of: Wednesday, March 29, 2000.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE00-00168 Final3/28/20003/29/20003/29/2000 12:00:00 AMAFAIL
###-#### NEC:210-52 (A) Recepticle outlet shall be required within. 6ft. of opening in linear wall. Called contractor. 3/29/00 12:00:40 PM
ELE00-00693 Electrical Rough-In3/28/20003/29/20003/29/2000 12:00:00 AMAPART
Alex ###-#### East & South walls Ele. R/I 3/29/00 12:01:42 PM
ELE99-02469 Electrical Rough-In3/28/20003/29/20003/29/2000 12:00:00 AMAPART
###-#### robert Conference: branch circuit code requirements. 3/29/00 12:01:12 PM
ELE00-00538 Final3/28/20003/29/20003/29/2000 12:00:00 AMAPASS
###-#### Completed 3/29/00 12:01:49 PM
ELE99-04436 Final3/28/20003/29/20003/29/2000 12:00:00 AMAPASS
###-#### Corrections completed. 3/29/00 12:01:28 PM
ELE00-01058 Temporary Service3/29/20003/29/20003/29/2000 12:00:00 AMPFAIL
###-#### Unused opening shall be sealed. Service entrance neutral conductor shall be insulated. 3/30/00 2:16:57 PM
ELE00-00599 Final3/29/20003/29/20003/29/2000 12:00:00 AMPPASS
pager ###-#### Completed. 3/30/00 2:17:11 PM
ELE99-02600 Final3/29/20003/29/20003/29/2000 12:00:00 AMPPASS
please call mark ferm at ###-#### Ok. 3/30/00 2:17:04 PM
ELE00-00168 Final3/29/20003/29/20003/29/2000 12:00:00 AMPFAIL
###-#### Not ready; called contractor. 3/30/00 2:16:28 PM
ELE00-00197 Final3/29/20003/29/20003/29/2000 12:00:00 AMPPART
###-#### pager Temp. occ. 3/30/00 2:17:19 PM