Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01075 Permanent Service3/29/20063/29/20063/29/2006 4:48:12 PMPFAIL
miles ###-#### called contr, left corr notice, 358.30(A) conduit shall be supported wihin 3' of box, 230.24(A) exception 3 clearance over roof shall be 18", (B) minimum clearance from grade shall be 10', BCC job id sticker shall be posted
ELE06-01076 Temporary Service3/29/20063/29/20063/29/2006 3:41:21 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
ELE06-01077 Temporary Service3/29/20063/29/20063/29/2006 2:38:30 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
ELE06-00960 Permanent Service3/28/20063/29/20063/29/2006 1:26:23 PMPPASS
scott; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s u/g rec ok
ELE05-04422 Final3/28/20063/29/20063/29/2006 11:58:48 AMPPASS
Scheduled by a contractor via Hello! on 3/28/2006 at 12:32:45 PM. Contact: ###-####. ok to final
ELE06-01025 Temporary Service3/28/20063/29/20063/29/2006 10:31:14 AMAFAIL
Clyde; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr notice, 250.50 grounding electrode system shall be installed, 250.24 grounding electrode conductor shall be connected to grounded conductor terminal
ELE06-00077 Final3/28/20063/29/20063/29/2006 10:10:42 AMPPASS
Scheduled by a contractor via Hello! on 3/28/2006 at 12:36:08 PM. Contact: ###-####. looked at sign, ok to final
ELE06-00833 Electrical Rough-In3/29/20063/29/20063/29/2006 9:24:43 AMAPART
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot walls called needs to correct 11/4" for ent and one green mc
ELE06-01060 Electrical Rough-In3/28/20063/29/20063/29/2006 9:02:59 AMAPASS
Chad; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, told about 1 1/4" 2 plcs, ric ok
ELE05-03294 Final3/28/20063/29/20063/29/2006 8:19:41 AMAPASS
Scheduled by a contractor via Hello! on 3/28/2006 at 8:33:01 AM. Contact: ###-####. ok to final