FIR05-00898
| INSP-Final Inspection | 3/27/2006 | 3/29/2006 | 3/29/2006 6:18:46 PM | P | FAIL |
|
|
Two in-duct detectors failed to function properly, horn in the charging room does not sound the temporal pattern required for fire alarm and conflicts with the temporal pattern of the horn in the office, need to provide NFPA 72 Inspection and Testing form, a copy of central station signal verification of items tested today including panel, sprinkler monitoring, detection and notification devices, alarms, supervisory, and troubles from 3:50 to 5:00 pm today to be available on site at next inspection for review.
|
FIR05-00542
| INSP-Final Inspection | 3/29/2006 | 3/29/2006 | 3/29/2006 6:08:38 PM | P | PASS |
|
|
Outstanding items have been completed, fire sprinkler finaled.
|
BLD04-02348
| FIRE-Conference | 3/28/2006 | 3/29/2006 | 3/29/2006 3:20:47 PM | P | DONE |
|
|
Stair presurization at 2:00pm; Phone #: ###-#### Internet Inspection Request from: Bob Thornton On site visit to verify stair test compliance with structural inspector.
|
FIR05-00594
| INSP-Sprinkler Rough-in/Hydro | 3/28/2006 | 3/29/2006 | 3/29/2006 3:15:27 PM | P | PART |
|
|
Hydrostatic test of the overhead wet, antifreeze, and standpipe systems is satisfactory, noted one head at the mezzanine stair landing is painted, head cage is missing at head under mezz ductwork, inspected the 5th and 6th floors for cover, the mech penthouse, 11th floor, and portions of the 1st floor are not inspected for cover at this time, discussed items left for completion at the riser room and final testing including standpipe flow test, forward flow of BFP and related sprinkler alarms.
|
FIR05-00297
| INSP-Sprinkler Rough-in/Hydro | 3/28/2006 | 3/29/2006 | 3/29/2006 1:52:38 PM | A | FAIL |
|
|
Flexible couplings are required on the 4" riser main above and below each floor penetration as the min. seismic clearance is not provided at these locations, the min. separation for heads at the east corner of each floor is exceeded.
|
FIR05-00372
| INSP-Final Inspection | 3/28/2006 | 3/29/2006 | 3/29/2006 12:57:51 PM | A | PASS |
|
|
Items on previous correction notices have been completed, fire sprinkler permit finaled.
|
MIS05-00093
| FIR-Final | 3/28/2006 | 3/29/2006 | 3/29/2006 11:37:04 AM | A | PASS |
|
|
Items on correction notice have been completed, inspection passed.
|
FIR06-00128
| INSP-Sprinkler Rough-in/Hydro | 3/28/2006 | 3/29/2006 | 3/29/2006 11:20:48 AM | A | PART |
|
|
UG fire supply line is good for cover, the target window on the post indicator shall be aligned parallel to the underground pipe per review notes and requirements of IFC 2003.
|
FIR06-00173
| INSP-Sprinkler Rough-in/Hydro | 3/29/2006 | 3/29/2006 | 3/29/2006 10:38:56 AM | A | PASS |
|
|
Overhead fire sprinkler work passed inspection, missing ceiling tiles at three locations to be installed today.
|
FIR06-00124
| INSP-Final Inspection | 3/28/2006 | 3/29/2006 | 3/29/2006 9:00:40 AM | A | PASS |
|
|
Fire alarm work is satisfactory, fire alarm passed inspection.
|
FIR05-00174
| INSP-Final Inspection | 3/28/2006 | 3/29/2006 | 3/29/2006 12:00:00 AM | P | CANC |
|
|
Kenny; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong /// Cancel per Kenny (Treasure Valley Fire Protection) and reschedule for 3-30 AM 3-29-06 eus
|