BLD06-02714
| FIRE-Final Inspection | 3/27/2007 | 3/29/2007 | 3/30/2007 2:49:02 PM | A | FAIL |
|
|
Need to install fire extinguishers at two locations, one exitsing door shown to be infilled on approved plans is not complete.
|
FIR06-00766
| INSP-Final Inspection | 3/27/2007 | 3/29/2007 | 3/30/2007 2:43:46 PM | A | PASS |
|
|
Fire sprinkler permit work passed final inspection.
|
FIR06-00721
| INSP-Final Inspection | 3/27/2007 | 3/29/2007 | 3/30/2007 2:41:54 PM | A | PASS |
|
|
Fire alarm passed final field inspection, noted modifications to the approved drawings tested acceptable, permit finaled.
|
FIR06-00307
| INSP-Final Inspection | 3/27/2007 | 3/29/2007 | 3/30/2007 2:39:26 PM | A | PASS |
|
|
Fire alarm work tested satisfactory, permit finaled.
|
FIR06-00523
| INSP-Alarm Testing | 3/28/2007 | 3/29/2007 | 3/29/2007 5:28:19 PM | A | FAIL |
|
|
FA inspection for the 4th floor only completed today, some defficiencies corrected while on site, other items in need of repair include non-functional SD 105 in the corridor, one SD at the SW corridor is overspaced, the fire damper at the north hall does not operate correctly, vending area lacks sufficient detector coverage, as-built plans do not show the deletion of two FD's.
|
FIR06-00731
| INSP-Final Inspection | 3/29/2007 | 3/29/2007 | 3/29/2007 5:19:12 PM | P | PASS |
|
|
Plans on site, reinspection passed, fire alarm permit finaled.
|
FIR07-00074
| INSP-Final Inspection | 3/29/2007 | 3/29/2007 | 3/29/2007 5:15:55 PM | P | PASS |
|
|
Fire alarm work is satisfactory, permit finaled.
|
MIS07-00057
| FIR-Final | 3/29/2007 | 3/29/2007 | 3/29/2007 5:14:57 PM | P | PASS |
|
|
Defficiencies amended, fire life safety inspection passed.
|
MIS07-00027
| FIR-Final | 3/29/2007 | 3/29/2007 | 3/29/2007 5:08:16 PM | P | PASS |
|
|
All items on the previous correction notice are finished, life safety is acceptable.
|
MIS07-00028
| FIR-Final | 3/29/2007 | 3/29/2007 | 3/29/2007 5:05:20 PM | P | PASS |
|
|
c/n items related to the racking have been verified for compliance, fire life safety finaled.
|
FIR06-00772
| INSP-Sprinkler Rough-in/Hydro | 3/29/2007 | 3/29/2007 | 3/29/2007 5:00:03 PM | P | DEFR |
|
|
Inspection rescheduled per conversation with contractor.
|
MIS07-00053
| FIR-Final | 3/28/2007 | 3/29/2007 | 3/29/2007 4:58:09 PM | A | PASS |
|
|
Inspection passed life safety.
|
BLD06-03206
| FIRE-Final Inspection | 3/28/2007 | 3/29/2007 | 3/29/2007 4:46:34 PM | A | PASS |
|
|
Correction is complete, final fire life safety inspection passed.
|