Inspections for the day of: Tuesday, March 29, 2011.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Johnson
TitlePLM-INSPECTOR
Phone #794-9476
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM11-00489 Plumbing Rough-in3/28/20113/29/20113/29/2011 5:08:04 PMPFAIL
Should be ready about 11 A.M. Phone #: ###-#### >> Inspection requested via web by Jason Gale need to provide tenting over water piping to over head shower. as per table 7-5 2003 upc no more than 1/3 of the total permitted length of any vent may be installed in a horizontal position 1 1/2 vent in overhead is too long
PLM11-00482 Groundwork3/28/20113/29/20113/29/2011 2:39:28 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Scott Hurren
PLM10-01467 PLM-Aging Inspection3/29/20113/29/20113/29/2011 1:55:14 PM PASS
PLM11-00477 Final3/28/20113/29/20113/29/2011 1:45:26 PMAPASS
Please call Johny with questions ###-####. Thank you Phone #: ###-#### >> Inspection requested via web by Jennifer Alcala
PLM10-02313 Other3/28/20113/29/20113/29/2011 1:15:34 PMAPART
9:00 am conference conf. only
PLM11-00116 PLM-Aging Inspection3/29/20113/29/20113/29/2011 10:28:26 AM PASS
PLM10-02650 PLM-Aging Inspection3/29/20113/29/20113/29/2011 10:27:48 AM PASS
no request for inspection
PLM10-01843 PLM-Aging Inspection3/29/20113/29/20113/29/2011 10:25:38 AM PASS
PLM10-01843 DOC - Permit Expired3/29/20113/29/20113/29/2011 10:25:24 AMAPASS
PLM11-00480 Final3/28/20113/29/20113/29/2011 10:22:15 AMAPASS
Shawn Phone #: ###-####