Inspections for the day of: Tuesday, March 29, 2011.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00072 FIR-Aging Inspection3/29/20113/29/20113/30/2011 2:50:07 PM PASS
FIR11-00014 INSP-Sprinkler Rough-in3/29/20113/29/20113/29/2011 3:32:24 PMPCANC
Wrong inspection type was called in. This was actually for alarm testing.
FIR11-00014 INSP-Alarm Testing3/29/20113/29/20113/29/2011 3:30:30 PMPDONE
The phase II fire alarm testing is complete. An item noted was any general smoke detector alarm would recall the elevator which is not allowed. I agreed to "sign off" for this phase II work but the elevator recall will need to be addressed prior to a final sign off on this project.
FIR11-00073 INSP-Final Inspection3/29/20113/29/20113/29/2011 3:22:50 PMPPASS
permit finaled
FIR10-00428 FIR-Aging Inspection3/29/20113/29/20113/29/2011 2:35:23 PM NR
Per Brian with Simplex, Charlie is working on getting the elevators done.
FIR10-00542 FIR-Aging Inspection3/29/20113/29/20113/29/2011 2:29:35 PM NR
work is in progress
BLD09-00414 FIRE-Final Inspection3/29/20113/29/20113/29/2011 2:28:52 PMPPASS
life safety passed
FIR11-00094 INSP-Sprinkler Rough-in3/29/20113/29/20113/29/2011 2:27:47 PMPPASS
sprinkler piping is ok to cover.
FIR10-00470 INSP-Sprinkler Rough-in/Hydro3/28/20113/29/20113/29/2011 2:26:24 PMPPASS
hydro for second floor passed.
BLD11-00381 FIRE-Final Inspection3/28/20113/29/20113/29/2011 9:38:22 AMAFAIL
Provide final inspection for the open FIR permit relating to the AES panel. Provide passage hardware to the restroom area and provide a ceiling in the small closet to act as a heat trap for the pendant sprinkler head.