BLD12-00197
| FIRE-Final Inspection | 3/27/2012 | 3/29/2012 | 3/30/2012 10:49:25 AM | P | FAIL |
|
|
Project is not ready for fire life safety final due to several items. Project related fire sprinkler and alarm permits need finaled, noted missing hardware at the main entry/exit, need to mount fire extinguishers, post max. occupant load sign, missing ceiling tile, no access at some areas due to floor finishes underway. Building lacks heat at the lower level- unit heaters are missing. Remote annunciator for the fire alarm control panel does not meet location criteria per title 7 section 510.2.
|
FIR12-00155
| INSP-Sprinkler Rough-in | 3/29/2012 | 3/29/2012 | 3/30/2012 10:40:25 AM | P | NR |
|
|
JEREMY Phone #: ###-#### *Note- no access to complete inspection due to jobsite conditions (floor sealant).
|
FIR11-00365
| INSP-Sprinkler Rough-in/Hydro | 3/28/2012 | 3/29/2012 | 3/30/2012 10:38:32 AM | A | FAIL |
|
|
System 8 hydrostatic test failed due to pressure loss at the gauge.
|
FIR12-00045
| INSP-Sprinkler Rough-in | 3/28/2012 | 3/29/2012 | 3/30/2012 10:36:13 AM | A | PART |
|
|
Previous correction items completed. Rough-in passed.
|
FIR11-00524
| INSP-Sprinkler Rough-in/Hydro | 3/28/2012 | 3/29/2012 | 3/30/2012 10:33:22 AM | A | PART |
|
|
System 4 overhead hydrostatic test passed. Completed re-inspection for relocated and added pendent heads at the AMH track areas. Noted missing hangers on three new arm-overs >2'.
|
FIR11-00448
| INSP-Sprinkler Rough-in/Hydro | 3/28/2012 | 3/29/2012 | 3/30/2012 10:27:37 AM | A | FAIL |
|
|
Overhead hydrostatic test failed due to pressure loss at the gauge. Noted re-inspection items include; plan resubmittal required due to: 18 additional upright heads not shown on the original design or included in the calculations, added 45's and 90's at the 4" grid mains, 2 1/2" main has been changed to 3", column protection is not included, missing longitudinal brace at mech. room 44, secure two retainers, upright coverage at the north mechanical access area is overspaced at 140ft2. Previous corrections finished are; sprig height at beams, axis adjustment, spacing at mechanical access 47 and south mech. access.
|
FIR11-00431
| INSP-Sprinkler Rough-in/Hydro | 3/28/2012 | 3/29/2012 | 3/30/2012 7:17:33 AM | A | FAIL |
|
|
Overhead hydrostatic test failed due to visible leakage on the system and pressure loss at the gauge. Re-inspection items noted include; lacking coverage at vestibule 100P- temporary bootie room (missing ceiling and sprinkler heads, outlets are plugged), SW stair 100W exit landing is partially sprinklered, missing field ceiling tile at the TEM labs, leak at non-clean link 100A, construction at the closet adjacent to RR 100F is incomplete, NW stair landing is partially sprinklered, missing ceiling and sprinkler coverage at non-clean link room 100T, missing ceiling tile at non-clean link, heads not installed at column line K temporary wall NE exit, missing head and ceiling at link intersections, secure retainer at dock corridor, noted 5 added uprights not shown on plans below dock area ductwork, plugged outlet and missing ceiling at GR 100H.
|
FIR11-00301
| INSP-Sprinkler Rough-in/Hydro | 3/28/2012 | 3/29/2012 | 3/30/2012 6:58:51 AM | A | FAIL |
|
|
Overhead hydrostatic test failed due to pressure loss at the gauge.
|