Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00870 FIRE-Conference3/14/20123/28/2012 A 
Please check on this and let Barb @ permit desk know status-want to try to close out permit-Thanks
FIR12-00134 INSP-Sprinkler Rough-in3/29/20123/29/20123/30/2012 10:56:34 AMPPASS
The sprinkler piping to the two pendant heads at the entrance can be covered.
FIR12-00107 INSP-Final Inspection3/29/20123/29/20123/30/2012 10:55:51 AMPPASS
Permit finaled
FIR12-00041 INSP-Sprinkler Rough-in3/29/20123/29/20123/29/2012 2:04:30 PMPPART
The sprinkler piping in the resident areas is ok to cover. Tenting is passed. The sprinkler piping in the garage areas has not had the insulation installed as Lonnie and I discussed so the piping in the garages can not be covered yet.
FIR11-00688 INSP-Final Inspection3/29/20123/29/20123/29/2012 1:49:36 PMPPASS
Permit finaled. EOL voltages verified.
FIR11-00683 INSP-Final Inspection3/29/20123/29/20123/29/2012 1:49:20 PMPPASS
Permit finaled. EOL voltages verified.
BLD12-00065 FIRE-Final Inspection3/29/20123/29/20123/29/2012 1:48:21 PMPPASS
Life safety passed.
FIR12-00123 INSP-Final Inspection3/29/20123/29/20123/29/2012 1:47:59 PMPPASS
Permit finaled
FIR11-00244 INSP-Final Inspection3/28/20123/29/20123/29/2012 1:47:00 PMAPASS
Permit finaled
FIR12-00054 INSP-Final Inspection3/28/20123/29/20123/29/2012 11:22:39 AMAFAIL
Baffles have not been installed yet.
FIR12-00120 INSP-Sprinkler Rough-in3/28/20123/29/20123/29/2012 10:45:54 AMAPART
Todays inspection was for the ULTA BEAUTY space. Everything appears ok except that the 3" and single 4" branchlines have 1 1/2" pieces in them located at the far main. I requested that TVFP get with plan review to verify that the hydraulic calculations are not adversely effected by this pipe size reduction. Also non-functional rack piping and sprinklers are still hanging from the structure.
BLD12-00065 FIRE-Final Inspection3/26/20123/29/20123/29/2012 9:51:46 AMAFAIL
The two exit signs failed to operate on backup power. All other items are ok.
FIR11-00688 INSP-Alarm Testing3/28/20123/29/20123/29/2012 9:49:40 AMAPASS
Testing complete
FIR11-00683 INSP-Alarm Testing3/28/20123/29/20123/29/2012 9:49:13 AMAPASS
Testing complete
BLD11-02773 FIRE-Final Inspection3/29/20123/29/20123/29/2012 9:47:57 AMAPASS
Life safety passed
FIR12-00023 INSP-Final Inspection3/29/20123/29/20123/29/2012 9:47:08 AMPPASS
Permit finaled. EOL voltage drops are acceptable.
FIR12-00023 INSP-Alarm Testing3/27/20123/29/20123/29/2012 9:46:37 AMAPASS
Permit finaled