BLD08-00870
| FIRE-Conference | 3/14/2012 | 3/28/2012 | | A | |
|
|
Please check on this and let Barb @ permit desk know status-want to try to close out permit-Thanks
|
FIR12-00134
| INSP-Sprinkler Rough-in | 3/29/2012 | 3/29/2012 | 3/30/2012 10:56:34 AM | P | PASS |
|
|
The sprinkler piping to the two pendant heads at the entrance can be covered.
|
FIR12-00107
| INSP-Final Inspection | 3/29/2012 | 3/29/2012 | 3/30/2012 10:55:51 AM | P | PASS |
|
|
Permit finaled
|
FIR12-00041
| INSP-Sprinkler Rough-in | 3/29/2012 | 3/29/2012 | 3/29/2012 2:04:30 PM | P | PART |
|
|
The sprinkler piping in the resident areas is ok to cover. Tenting is passed. The sprinkler piping in the garage areas has not had the insulation installed as Lonnie and I discussed so the piping in the garages can not be covered yet.
|
FIR11-00688
| INSP-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 1:49:36 PM | P | PASS |
|
|
Permit finaled. EOL voltages verified.
|
FIR11-00683
| INSP-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 1:49:20 PM | P | PASS |
|
|
Permit finaled. EOL voltages verified.
|
BLD12-00065
| FIRE-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 1:48:21 PM | P | PASS |
|
|
Life safety passed.
|
FIR12-00123
| INSP-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 1:47:59 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00244
| INSP-Final Inspection | 3/28/2012 | 3/29/2012 | 3/29/2012 1:47:00 PM | A | PASS |
|
|
Permit finaled
|
FIR12-00054
| INSP-Final Inspection | 3/28/2012 | 3/29/2012 | 3/29/2012 11:22:39 AM | A | FAIL |
|
|
Baffles have not been installed yet.
|
FIR12-00120
| INSP-Sprinkler Rough-in | 3/28/2012 | 3/29/2012 | 3/29/2012 10:45:54 AM | A | PART |
|
|
Todays inspection was for the ULTA BEAUTY space. Everything appears ok except that the 3" and single 4" branchlines have 1 1/2" pieces in them located at the far main. I requested that TVFP get with plan review to verify that the hydraulic calculations are not adversely effected by this pipe size reduction. Also non-functional rack piping and sprinklers are still hanging from the structure.
|
BLD12-00065
| FIRE-Final Inspection | 3/26/2012 | 3/29/2012 | 3/29/2012 9:51:46 AM | A | FAIL |
|
|
The two exit signs failed to operate on backup power. All other items are ok.
|
FIR11-00688
| INSP-Alarm Testing | 3/28/2012 | 3/29/2012 | 3/29/2012 9:49:40 AM | A | PASS |
|
|
Testing complete
|
FIR11-00683
| INSP-Alarm Testing | 3/28/2012 | 3/29/2012 | 3/29/2012 9:49:13 AM | A | PASS |
|
|
Testing complete
|
BLD11-02773
| FIRE-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 9:47:57 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00023
| INSP-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 9:47:08 AM | P | PASS |
|
|
Permit finaled. EOL voltage drops are acceptable.
|
FIR12-00023
| INSP-Alarm Testing | 3/27/2012 | 3/29/2012 | 3/29/2012 9:46:37 AM | A | PASS |
|
|
Permit finaled
|