Inspections for the day of: Tuesday, March 29, 2016.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00955 Temporary Service3/29/20163/29/20163/29/2016 3:04:13 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE16-00954 Temporary Service3/29/20163/29/20163/29/2016 2:58:48 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE16-00942 Electrical Rough-In3/29/20163/29/20163/29/2016 2:18:04 PMPFAIL
If you have any questions, please call Clay. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
Unable to inspect due to BLDG permit is under review. when issued recall.
320.23- Where cables are run within 7' of attic access install guard strip to protect from physical damage.
ELE16-00440 Final3/28/20163/29/20163/29/2016 1:35:57 PMPFAIL
Call if you need access lock box on front door. Phone #: ###-#### Inspection requested via web by robert feller
110.3- Items shall be wired as per manufacturers instructions. Receptacle in light grey room not working. Fans located in shower stalls shall have GFCI protection..
330.30- MC and flex in millwork or cash wrap shall be secured within 12" of each box.
406.5(D)- Receptacles shall be flush or project from faceplate. Diamond plate areas.
422.30- A disconnecting means shall be provided for tanning bed. 110.25 lockout acceptable. Wiring compartment open.
422.52- Drinking fountain shall have GFCI protection. Unable to locate.
ELE16-00940 Final3/29/20163/29/20163/29/2016 1:14:52 PMPPASS
Lighting retro complete. Final ok
ELE13-01393 ELE-Aging Inspection3/29/20163/29/20163/29/2016 12:09:32 PM PASS
Waiting on contractorq
ELE13-02193 ELE-Aging Inspection3/29/20163/29/20163/29/2016 11:24:24 AM PASS
Still under construction
MIS16-00077 ELE-Final3/29/20163/29/20163/29/2016 11:14:16 AMPPASS
Check for permit for electrical
Work cover underELE16-00942. Final ok
ELE15-03396 Electrical Rough-In3/28/20163/29/20163/29/2016 11:12:47 AMAPASS
We need a ceiling inspection, please. Thank you1 Phone #: ###-#### Inspection requested via web by Stacie Tasker
Customer lounge hardlid rough in ok cover
ESC15-01622 General Inspection3/29/20163/29/20163/29/2016 11:11:57 AMPPASS
Lot clean some landscape complete. ok
ESC15-01562 General Inspection3/29/20163/29/20163/29/2016 11:10:58 AMPPASS
Trash contained ok
ELE16-00940 Electrical Rough-In3/29/20163/29/20163/29/2016 10:40:26 AMAPASS
rough in on lighting retrofit Phone #: ###-#### Inspection requested via web by Tim Dunlop Listing confirmed. Rough in ok
ELE15-03437 Final3/28/20163/29/20163/29/2016 10:18:45 AMAPASS
Key inside recep at front porch Phone #: ###-#### Inspection requested via web by Robert Schroder Final ok
ELE16-00956 Temporary Service3/28/20163/29/20163/29/2016 9:46:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE16-00407 Final3/25/20163/29/20163/29/2016 9:24:17 AMAFAIL
garage code.....4200 Phone #: ###-#### Inspection requested via web by Will Sevy
110.3- Devices shall be wired as per manufacturers instructions. Hall 3-way.
314.20- Where box is mounted in combustible materials boxes shall be flush or an extension shall be installed. Outdoor outlets.
406.5- Receptacles shall be secured to box. Front outdoor receptacle.
410.16- Luminaire that can accept incandescent lamps shall not be installed less than 12" of shelf.
ELE16-00337 Final3/29/20163/29/20163/29/2016 8:46:44 AMAPASS
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok