Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00705 Final3/29/20173/29/20173/29/2017 2:14:46 PMPPASS
Altenergy contact ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller Final ok
ELE17-00705 Electrical Rough-In3/29/20173/29/20173/29/2017 2:14:25 PMPPASS
Altenergy contact ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller Rough in ok.
ELE17-00814 Final3/28/20173/29/20173/29/2017 2:13:38 PMPPASS
Will Call you at 12PM to schedule a time to meet you onsite! Phone #: ###-#### Inspection requested via web by Matthew Dunay Final ok
ELE17-00814 Electrical Rough-In3/29/20173/29/20173/29/2017 2:13:29 PMPPASS
Will Call you at 12PM to schedule a time to meet you onsite! Phone #: ###-#### Inspection requested via web by Matthew Dunay
Listing confirmed. Bonding with CO/ALR lugs to array rack. Rough in ok
Li
ELE17-00822 Permanent Service3/29/20173/29/20173/29/2017 12:06:32 PMAFAIL
Do not final out permit // Casey Phone #: ###-####
BCC 4-05-31(C)- Unfused conductors shall not run inside a structure unless for underground service entrance conductors for a recessed meter with 4 1/2' max length. 230.70- service disconnecting means shall be on outside or immediately on interior of structure.
230.28- Overhead service entrance conductors shall not attach to mast between weather head and a coupling.
ELE17-00740 Final3/28/20173/29/20173/29/2017 11:57:03 AMAPASS
Please call with any questions. Phone #: ###-#### Inspection requested via web by Casey Fouts
Final ok on service change
ELE17-00502 Final3/28/20173/29/20173/29/2017 10:48:22 AMAFAIL
Jeremy is contact Phone #: ###-#### Inspection requested via web by Ryan Wake
210.8(B)- All 20 amp 120 volt receptacle outlets located in kitchen areas shall have GFCI protection. Double duplex under countertop left of range.
210.62- Show window receptacles shall be located with in 18" of top of windows for each 12 linear ft or major fraction thereof show window area measured horizontally.
Called left message
ELE16-03479 Final3/28/20173/29/20173/29/2017 9:44:36 AMAFAIL
Von. Phone #: ###-#### Inspection requested via web by Sean DeLacy
210.8(B)- All 120 volt 15 and 20 amp receptacle outlets located within 6' of a sink shall have GFCI protection. All exam rooms TV outlets all above 6'7" not readily accessible and south exams have lower receptacles within 6'