Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00670 Final3/29/20193/29/20193/29/2019 2:23:00 PMPPASS
Electrical demo for roof demo and rebuild is completed per permit. Phone #: ###-#### Inspection requested via web by Jim Noll
Wiring removed so roof system can be replaced. No work other than demo under this permit. Final ok
ELE19-00888 Final3/29/20193/29/20193/29/2019 2:05:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Jim Noll
Final ok
ELE17-01549 Final3/29/20193/29/20193/29/2019 1:35:56 PMPPASS
Electrical final
Shane McKissen is the contact Phone #: ###-#### Inspection requested via web by Shawna Gates Final ok
ELE19-00424 Final3/25/20193/29/20193/29/2019 10:59:54 AMAFAIL
code 2468 Phone #: ###-#### Inspection requested via web by Icon Electric
Charged a $55 fee for 200 amp service as noted but job is for a 2700 square ft residence that requires $135 fee. Recall when corrected. House checked out OK.
ELE19-00306 Final3/29/20193/29/20193/29/2019 10:59:40 AMPPART
Temp final for main level only, basement needs electrical safed off. Approval of main floor to allow TI permits to proceed. Corrections to be completed 4-1-19.
ELE19-00306 Final3/28/20193/29/20193/29/2019 10:24:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ryan Wake
BCC 4 05 32- Code violations not to be retained,
Basement area.
314.23- All boxes shall be secured to structure.
314,25- All boxes shall have covers.
330.30- MC and flex shall be secured and supported.
358.30- EMT shall be supported and secured.
400.12- Flexible cords shall not be used for structural wiring. Basement bath fan.
406.6- All receptacles shall have covers.
Main level check out OK.
ELE19-00913 Electrical Rough-In3/28/20193/29/20193/29/2019 9:43:28 AMAPASS
AJ Phone #: ###-####
Discussed 210.71 meeting rooms. 1 meeting room in basement will require 2 floor receptacles. Wall rough in ok cover
ELE19-01088 Electrical Rough-In3/28/20193/29/20193/29/2019 9:09:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Perez
Perimeter walls rough in ok cover