Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00107 INSP-Sprinkler Rough-in3/3/20053/3/20053/3/2005 12:00:00 AM FAIL
Inspection was for vaulted ceiling in the elevator lobby. The sprinkler piping on plans is 1 1/4" but piping is actually 1". Notified contractor that the piping laying on top of the soffits must meet nfpa 13 requirements for hanging. I could bent the soffit with my own weight. 3/3/2005 12:33:05 PM
FIR04-00774 INSP-Alarm Testing2/28/20053/3/20053/3/2005 12:00:00 AMAPASS
fire alarm finaled 3/3/2005 12:33:50 PM
FIR04-00666 INSP-Sprinkler Rough-in/Hydro3/2/20053/3/20053/3/2005 12:00:00 AMAPART
First floor center section of the building is ok to cover. Insulation is not being added. 3/3/2005 1:49:30 PM
FIR04-00684 INSP-Supply line flush3/3/20053/3/20053/3/2005 12:00:00 AMAPART
Underground supply piping is ok to cover. Notified contractor that a tamper switch would be needed for the Post Indicator Valve. 3/3/2005 1:18:56 PM
BLD04-02509 FIRE-Final Inspection3/3/20053/3/20053/3/2005 12:00:00 AMPCANC
Door hardware not installed yet. To be rescheduled 3/3/2005 3:52:11 PM
FIR04-00807 INSP-Sprinkler Rough-in/Hydro3/3/20053/3/20053/3/2005 12:00:00 AMPPART
Piping in room southwest of stairs can be covered. Per contractor plans are being resubmitted to show changes in piping. 3/3/2005 3:51:35 PM