Inspections for the day of: Friday, March 3, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00060 INSP-Sprinkler Rough-in3/2/20063/3/20063/3/2006 4:57:29 PMADEFR
Inspection to be completed 3/6 per agreement.
FIR05-00152 INSP-Sprinkler Rough-in/Hydro3/2/20063/3/20063/3/2006 4:56:19 PMADEFR
Wrong permit number called in, was intended for a pump test on the overhead, noted that the sensing lines are incorrectly piped.
FIR05-00659 INSP-Sprinkler Rough-in/Hydro3/3/20063/3/20063/3/2006 3:04:10 PMPPART
Overhead hydrostatic test of the new 3" wet system at the office area is acceptable.
BLD01-01632 FIRE-Final Inspection3/3/20063/3/20063/3/2006 3:02:28 PMPFAIL
Provide a fire extinguisher within allowable travel distance per IFC 2003, provide directional arrows at the exit signs in the hallway adjacent to the stairway, need to test the delayed egress locks on loss of power, alarm activation, and normal operation, need to verify emergency lighting at the vicinity of the delayed egress doors and for path of egress.
FIR06-00027 INSP-Final Inspection3/3/20063/3/20063/3/2006 1:30:03 PMPPASS
Required correction was completed on site, fire alarm permitted work is acceptable, inspection passed.
FIR05-00330 INSP-Alarm Testing2/28/20063/3/20063/3/2006 1:21:55 PMAPART
Indicate added av in the office on 11th floor on as builts, 9th floor is missing notification in the confrence room and short hall, verify cd and dB in the server room on 9th, "server" room is now a break room on the 8th, show deleted av in the storage room on 7th, add av in the confrence room on 6th, delete high partition or add visual coverage at common area on 6th, adjust door closures at south end on 5th floor, show all required changes on approved plans for verification at next inspection.
FIR04-00166 INSP-Alarm Testing2/28/20063/3/20063/3/2006 1:11:30 PMAPART
Provide resubmittals for changes in the basement (Angels), provide updated building map, add notification in the break room on 8th floor.
FIR05-00048 INSP-Alarm Testing2/28/20063/3/20063/3/2006 1:07:15 PMAPART
The "server" room is now being used as a break room which will require notification, provide as builts reflecting changes.
FIR06-00035 INSP-Alarm Testing3/3/20063/3/20063/3/2006 12:00:00 AMPCANC
BRYAN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles - NEEDS TO BE CANCELLED TO ELEC