FIR06-00060
| INSP-Sprinkler Rough-in | 3/2/2006 | 3/3/2006 | 3/3/2006 4:57:29 PM | A | DEFR |
|
|
Inspection to be completed 3/6 per agreement.
|
FIR05-00152
| INSP-Sprinkler Rough-in/Hydro | 3/2/2006 | 3/3/2006 | 3/3/2006 4:56:19 PM | A | DEFR |
|
|
Wrong permit number called in, was intended for a pump test on the overhead, noted that the sensing lines are incorrectly piped.
|
FIR05-00659
| INSP-Sprinkler Rough-in/Hydro | 3/3/2006 | 3/3/2006 | 3/3/2006 3:04:10 PM | P | PART |
|
|
Overhead hydrostatic test of the new 3" wet system at the office area is acceptable.
|
BLD01-01632
| FIRE-Final Inspection | 3/3/2006 | 3/3/2006 | 3/3/2006 3:02:28 PM | P | FAIL |
|
|
Provide a fire extinguisher within allowable travel distance per IFC 2003, provide directional arrows at the exit signs in the hallway adjacent to the stairway, need to test the delayed egress locks on loss of power, alarm activation, and normal operation, need to verify emergency lighting at the vicinity of the delayed egress doors and for path of egress.
|
FIR06-00027
| INSP-Final Inspection | 3/3/2006 | 3/3/2006 | 3/3/2006 1:30:03 PM | P | PASS |
|
|
Required correction was completed on site, fire alarm permitted work is acceptable, inspection passed.
|
FIR05-00330
| INSP-Alarm Testing | 2/28/2006 | 3/3/2006 | 3/3/2006 1:21:55 PM | A | PART |
|
|
Indicate added av in the office on 11th floor on as builts, 9th floor is missing notification in the confrence room and short hall, verify cd and dB in the server room on 9th, "server" room is now a break room on the 8th, show deleted av in the storage room on 7th, add av in the confrence room on 6th, delete high partition or add visual coverage at common area on 6th, adjust door closures at south end on 5th floor, show all required changes on approved plans for verification at next inspection.
|
FIR04-00166
| INSP-Alarm Testing | 2/28/2006 | 3/3/2006 | 3/3/2006 1:11:30 PM | A | PART |
|
|
Provide resubmittals for changes in the basement (Angels), provide updated building map, add notification in the break room on 8th floor.
|
FIR05-00048
| INSP-Alarm Testing | 2/28/2006 | 3/3/2006 | 3/3/2006 1:07:15 PM | A | PART |
|
|
The "server" room is now being used as a break room which will require notification, provide as builts reflecting changes.
|
FIR06-00035
| INSP-Alarm Testing | 3/3/2006 | 3/3/2006 | 3/3/2006 12:00:00 AM | P | CANC |
|
|
BRYAN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles - NEEDS TO BE CANCELLED TO ELEC
|