Inspections for the day of: Monday, March 3, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01932 FIRE-Conference3/3/20083/3/20083/4/2008 6:44:08 PMPDONE
On site conference regarding questions related to the building fire alarm system specific to manual pull station locations, in duct detectors and plan review annotations.
FIR07-00813 INSP-Final Inspection3/3/20083/3/20083/4/2008 7:44:07 AMPDEFR
bill Phone #: ###-####
FIR07-00854 INSP-Sprinkler Rough-in/Hydro3/3/20083/3/20083/3/2008 4:36:40 PMPFAIL
Wrong permit number called in for inspection, was intended for the project related overhead permit work- Completed a preliminary walkthrough while on site of the narthex and sanctuary area-see approved plans for annotations. Noted main pipe size discrepancy at one area, CPVC piping has been used for several branchlines but no indication is made to that affect on the plans or review notes.
FIR07-00813 INSP-Supply line flush3/3/20083/3/20083/3/2008 3:44:44 PMPDEFR
To be completed on 3/4 as discussed.
BLD07-02852 FIRE-Final Inspection2/29/20083/3/20083/3/2008 3:43:36 PMPPASS
Noted items from the previous inspection have been completed including door hardware, exit sign repair and provision of a current annual inspection for the existing fire sprinkler system. Fire life safety passed.
FIR08-00091 INSP-Final Inspection3/3/20083/3/20083/3/2008 3:41:11 PMPPASS
Duct detectors at two locations have been removed due to HVAC capacities below limits required for device installation.
FIR08-00050 INSP-Final Inspection3/3/20083/3/20083/3/2008 3:35:41 PMPPASS
Fire sprinkler permit finaled.
FIR08-00156 INSP-Sprinkler Rough-in3/3/20083/3/20083/3/2008 3:06:01 PMPPART
Okay to cover fire sprinkler system modifications at the drop ceilings.
BLD07-02852 FIRE-Final Inspection3/3/20083/3/20083/3/2008 3:00:45 PMPDONE
Duplicate inspection request.
FIR07-00827 INSP-Sprinkler Rough-in2/29/20083/3/20083/3/2008 12:24:45 PMAPART
OH install is approved for cover as initialed on plans, need verification of pipe routing for the existing 2 1/2" main due to supply and termination points not matching plan set.
FIR07-00086 INSP-Sprinkler Rough-in2/29/20083/3/20083/3/2008 12:21:54 PMAPART
See areas marked with today's date on approved plans okayed for cover, field modifications due to floor plan changes accepted.
FIR07-00964 FIR-Aging Inspection3/3/20083/3/20083/3/2008 11:37:02 AM DEFR
Need site inspection request.
BLD07-03041 FIRE-Final Inspection3/3/20083/3/20083/3/2008 11:35:30 AMAPASS
Life safety finaled.
FIR08-00072 INSP-Final Inspection2/29/20083/3/20083/3/2008 11:33:57 AMAPART
Fire alarm system testing completed satisfactory, final pending the addition of one notification device at the shower area and removal of existing single station smoke alarms at various locations thruought.
FIR07-00813 INSP-Supply line flush2/29/20083/3/20083/3/2008 11:26:49 AMANR
UG flush rescheduled per contractor.
BLD04-02484 FIRE-Conference3/3/20083/3/20083/3/2008 11:25:24 AMADONE
Harvey Phone# ###-####
BLD08-00314 FIRE-Final Inspection2/29/20083/3/20083/3/2008 12:00:00 AMACANC
ben shalz--call 1st before insp Phone #: ###-####