Inspections for the day of: Tuesday, March 3, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00070 FIRE-Final Inspection3/3/20093/3/20093/3/2009 4:13:03 PMPPASS
Fire life safety site inspection passed.
FIR09-00144 INSP-Final Inspection3/3/20093/3/20093/3/2009 4:08:13 PMPPASS
Scope of demo work per permit documents verified for completion, permit finaled.
FIR08-00699 INSP-Sprinkler Rough-in3/2/20093/3/20093/3/2009 3:42:31 PMAPART
Inspection for overhead work at sheetrock ceilings in restrooms area "A" approved for cover-locations also marked on plans. Also discussed exceptions allowed per NFPA 13 for non-sprinklered canopies and concealed spaces at the exterior portions of the building.
FIR08-00018 INSP-Sprinkler Rough-in/Hydro3/2/20093/3/20093/3/2009 3:19:44 PMAFAIL
See areas red-lined on approved plans for locations at the basement level system in need of adjustment including one missing upright, heads at the vicinity of two unit heaters will require a higher temp rating, one EQ brace is not attatched, provide a head cage at the upright below the stairs, one SW head is too low, the electrical room and one storage room are not yet finished and have changed floorplan/piping layout-will need record drawings indicating field modifications. Also inspected the 10th floor common corridor-OH is approved for cover, noted blockage of one head by an exit sign which can be relocated. Noted sw head coverage at the elevator pit to be adjusted to avoid obstructions to discharge by equipment.
FIR08-00863 INSP-Supply line flush3/2/20093/3/20093/3/2009 1:57:10 PMAPART
Underground fire supply line flush completed satisfactory.
BLD08-02249 FIRE-Final Inspection3/2/20093/3/20093/3/2009 10:33:10 AMAPART
Apt. unit 544 fire life safety okayed.
BLD09-00018 FIRE-Final Inspection3/2/20093/3/20093/3/2009 10:31:38 AMAPART
Unit 528 life safety inspection passed.
FIR08-00768 FIR-Aging Inspection3/3/20093/3/20093/3/2009 9:53:03 AM DONE
Work in progress, construction underway.
FIR08-00766 INSP-Sprinkler Rough-in/Hydro3/2/20093/3/20093/3/2009 9:51:11 AMAPART
See approved plan set for locations of three thrust blocks at tee's feeding system risers okayed for cover marked with today's date.