Inspections for the day of: Tuesday, March 3, 2015.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00778 INSP-Sprinkler Rough-in3/2/20153/3/20153/6/2015 2:45:39 PMPPART
FIR14-00708 INSP-Sprinkler Rough-in3/2/20153/3/20153/6/2015 2:44:57 PMPPART
FIR14-00344 INSP-Sprinkler Rough-in3/2/20153/3/20153/3/2015 4:38:39 PMPPART
Completed overhead inspection for cover at the 2nd floor building areas A, B, and C for sheetrock lids at the corridor, service use rooms, and common areas as marked and dated on approved plans. Items noted include; one head to be relocated, missing hanger at the 2" main in housekeeping, relocate capped drop, SW heads at area A in three locations are not yet installed. Discussed max head spacing at the corridors, locations per plan where standard pendent heads are to be provided, proximity of light fixture junction boxes to sprinklers.
BLD14-03308 FIRE-Final Inspection3/2/20153/3/20153/3/2015 4:31:20 PMPPASS
Fire life safety inspection completed acceptable. Need to post tenant space suite address numbers prior to structural final as discussed.
FIR15-00101 INSP-Final Inspection3/2/20153/3/20153/3/2015 4:29:38 PMPPASS
Fire alarm testing completed satisfactory. As-builts recieved.
FIR15-00016 INSP-Final Inspection3/2/20153/3/20153/3/2015 4:28:37 PMPPASS
Fire sprinkler permit finaled.