ELE16-00674
| Final | 3/3/2016 | 3/3/2016 | 3/3/2016 3:41:54 PM | P | NR |
|
|
Please inspect sign wiring. Phone #: ###-#### Inspection requested via web by ERIC CENTERS Underground going in at time of inspection
|
ELE16-00674
| Electrical Rough-In | 3/3/2016 | 3/3/2016 | 3/3/2016 3:41:08 PM | P | PASS |
|
|
Please inspect sign wiring. Phone #: ###-#### Inspection requested via web by ERIC CENTERS Underground rough in ok cover
|
ELE16-00136
| Final | 3/3/2016 | 3/3/2016 | 3/3/2016 3:00:46 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
ELE15-03489
| Final | 3/3/2016 | 3/3/2016 | 3/3/2016 1:44:55 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS 110.7- Exam 8 GFCI not working, wireman found screw in MC from fire box installation.
|
ELE16-00166
| Final | 3/3/2016 | 3/3/2016 | 3/3/2016 1:32:15 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
ELE16-00372
| Final | 3/3/2016 | 3/3/2016 | 3/3/2016 12:23:46 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe 408.41- Each grounded conductor shall terminate in the panelboard in an individual terminal that is not also used to another conductor.
|
ELE13-01339
| ELE-Aging Inspection | 3/3/2016 | 3/3/2016 | 3/3/2016 11:26:40 AM | | PASS |
|
|
Contractor will check on job and call with results.
|
ELE16-00596
| Electrical Rough-In | 3/2/2016 | 3/3/2016 | 3/3/2016 10:50:07 AM | A | PASS |
|
|
BONDING/GROUNDING INSPECTION Phone #: ###-#### Inspection requested via web by CHRIS CARMINE Underground ight to shop, bonding of metal frame, 4 points for perimeter, light and ladder. Rough in ok cover
|
ELE16-00513
| Final | 3/2/2016 | 3/3/2016 | 3/3/2016 10:06:23 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jonathan Poot Final ok
|
ELE16-00203
| Electrical Rough-In | 3/2/2016 | 3/3/2016 | 3/3/2016 9:25:11 AM | A | CANC |
|
|
Jose Phone #: ###-#### Needed conference
|
ELE16-00203
| Conference | 3/3/2016 | 3/3/2016 | 3/3/2016 9:24:42 AM | P | DONE |
|
|
Jose Phone #: ###-#### Discussed required grounding electrode system for new fire pump service. They poured and concrete encased in floor of new fire pump room. Shall use all available grounding electrodes. Fire pump underground metal piping system, concrete encased, contractor to ensure main service grounding electrode system bonds to fire sprinkler piping system to tie all together.
|
ELE16-00659
| Temporary Service | 3/2/2016 | 3/3/2016 | 3/3/2016 8:49:46 AM | A | PASS |
|
|
Temp pole Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
|