Inspections for the day of: Thursday, March 3, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-02730 FIRE-Final Inspection3/2/20163/3/20163/3/2016 3:10:59 PMAPASS
Previously noted items repaired. Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers have current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00020 INSP-Final Inspection3/3/20163/3/20163/3/2016 1:50:28 PMPPASS
Final fire alarm inspection for elevator passed/complete.
FIR16-00020 INSP-Sprinkler Rough-in/Hydro3/2/20163/3/20163/3/2016 1:48:25 PMPCANC
Inspection request is for a fire alarm final, not a sprinkler rough-in/hydro, cancelling this inspection request and generating the correct request.
FIR16-00071 INSP-Final Inspection3/3/20163/3/20163/3/2016 12:43:49 PMPPASS
Hydrostatic test, 2 hours @ 200 psi passed/complete for overhead sprinkler piping
FIR15-00796 INSP-Sprinkler Rough-in3/2/20163/3/20163/3/2016 12:17:18 PMPPASS
Tenting inspection for 2nd level passed/complete, overhead piping for second level approved for cover.
FIR15-00701 INSP-Supply line flush3/1/20163/3/20163/3/2016 12:16:26 PMADONE
Underground main supply flush complete.
FIR15-00796 INSP-Supply line flush3/1/20163/3/20163/3/2016 12:16:00 PMADONE
Underground main supply flush complete.
BLD15-02692 FIRE-Final Inspection3/2/20163/3/20163/3/2016 9:41:05 AMPPASS
Fire sprinkler inspection complete, no fire alarms, fire extinguishers have current inspection tags. Final life fire safety inspection passed/complete.
FIR15-00575 INSP-Final Inspection3/2/20163/3/20163/3/2016 9:38:06 AMAPASS
Final fire sprinkler inspection passed/complete.