ELE04-01163
| ELE-Aging Inspection | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | | PASS |
|
|
ok corrections made 3/30/2005 7:54:12 AM
|
ELE04-01349
| ELE-Aging Inspection | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | | CANC |
|
|
called contractor has never got back to me 3/30/2005 7:17:55 AM
|
ELE04-01475
| ELE-Aging Inspection | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | | CANC |
|
|
no response back from contractor 3/30/2005 7:17:12 AM
|
ELE05-01016
| Electrical Rough-In | 3/29/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 3/29/2005 at 3:14:57 PM. Contact: ###-####. u/g ok corrections made 3/30/2005 7:35:29 AM
|
ELE05-00141
| Final | 3/29/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/29/2005 at 3:26:10 PM. Contact: ###-####. cor. posted called 314.23(D)(2)&300.11(A) support boxes and cables, 330.30(B&C) & 300.11 support cables and raceways 358.30(A) 400.8(5) no cords above ceiling, 314.27(D) listed fan boxes needed, seal opening in sub panel, 3/30/2005 11:32:35 AM
|
ELE05-01054
| Electrical Rough-In | 3/29/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PASS |
|
|
###-#### - darrell ok 3/30/2005 9:52:00 AM
|
ELE05-01055
| Electrical Rough-In | 3/29/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PASS |
|
|
###-#### - darrell ok 3/30/2005 9:52:35 AM
|
ELE05-01056
| Electrical Rough-In | 3/29/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PASS |
|
|
###-#### - darrell ok 3/30/2005 9:53:02 AM
|
ELE05-01054
| Permanent Service | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE05-01055
| Permanent Service | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE05-01056
| Permanent Service | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE05-01057
| Permanent Service | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | A | PASS |
|
|
p/s u/g new ok
|
ELE04-03671
| Electrical Rough-In | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | PART |
|
|
ceiling grid-- alan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok, needs listed fan box or support fan to structure, need to check listing of track lighting cord fed 3/30/2005 12:51:52 PM
|
ELE04-03527
| Final | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ceiling ok needs fan boxes or support fans from structure, check listeng on cord fed track lighting 3/30/2005 12:49:09 PM
|
ELE04-03527
| Final | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | NR |
|
|
called 3/30/2005 4:32:34 PM
|
ELE05-01049
| Electrical Rough-In | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | FAIL |
|
|
cor. posted 210.52(A) shall provide required outlet spacing for downstairs bed remodel, and new room added above garage, shall expose, or remove all wiring done by owner without inspection, note need approved plans at job site 3/30/2005 2:39:02 PM
|
ELE05-01057
| Electrical Rough-In | 3/29/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | PASS |
|
|
###-#### - darrell ok 3/30/2005 9:53:30 AM
|
ELE05-01051
| Final | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | PASS |
|
|
Call Elma to meet, ###-####.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok 3/30/2005 1:23:36 PM
|
ELE05-01065
| Permanent Service | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | FAIL |
|
|
THANK YOU ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH cor. posted called needs all grd and bonding complete water system, steel structure, other metal piping 3/30/2005 3:24:28 PM
|
ELE05-00420
| Final | 3/30/2005 | 3/30/2005 | 3/30/2005 12:00:00 AM | P | PASS |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie final ok for r/i work only, done by MtnPower, owner secured new permit,ele05-01049, to finish job 3/30/2005 2:23:41 PM
|