Inspections for the day of: Wednesday, March 30, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01046 Rough-In Permanent Service3/29/20053/30/20053/30/2005 12:00:00 AMAPASS
###-#### ric ok p/s u/g n ok 3/30/2005 8:49:08 AM
ELE05-00832 Electrical Rough-In3/29/20053/30/20053/30/2005 12:00:00 AMAPASS
###-#### Jerry ric ok for room addition 3/30/2005 9:43:36 AM
ELE05-00554 Electrical Rough-In3/29/20053/30/20053/30/2005 12:00:00 AMANH
please contact Duane, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called left message, don't know what to look at 3/30/2005 8:28:30 AM
ELE05-01048 Electrical Rough-In3/29/20053/30/20053/30/2005 12:00:00 AMAPASS
###-#### - brandon called, left message, told about 1 1/4" and that I marked several places . Left survey. BCC job id shall be posted, 300.4(D) ric ok, 3/30/2005 9:56:56 AM
ELE05-01048 Permanent Service3/30/20053/30/20053/30/2005 12:00:00 AMAPASS
p/s u/g n ok
ELE05-01041 Electrical Rough-In3/29/20053/30/20053/30/2005 12:00:00 AMAFAIL
###-#### dennis called left message and corr notice. 250.24(A)(1) gec shall be connected to grounded conductor lug, 110.12(A) unused openings shall be closed in panel, 314.23(C)(1) boxes shall be attached to framing members in new work 3/30/2005 8:15:02 AM
ELE04-03683 Electrical Rough-In3/30/20053/30/20053/30/2005 12:00:00 AMPNR
craig - ###-#### called contr and said all make-up to be done and mud rings before inspection 3/30/2005 1:40:07 PM
ELE05-00639 Final3/30/20053/30/20053/30/2005 12:00:00 AMPPART
please call to set time; Phone #: ###-#### Internet Inspection Request from: Nikki Day met with elect, they are adding some straps and gfci protection in the kitchen area. 3/30/2005 1:07:27 PM
ELE05-00423 Final3/30/20053/30/20053/30/2005 12:00:00 AMPPASS
###-#### - kim ok to final 3/30/2005 4:43:02 PM
ELE05-01047 Permanent Service3/30/20053/30/20053/30/2005 12:00:00 AMPPASS
p/s u/g n ok
ELE05-01050 Electrical Rough-In3/29/20053/30/20053/30/2005 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 3/29/2005 at 4:56:10 PM. Contact: ###-####. main pool bond ok to cover,need to check equi-potential plane before done 3/30/2005 4:45:10 PM
ELE05-01047 Electrical Rough-In3/29/20053/30/20053/30/2005 12:00:00 AMPPASS
###-#### rob called contr about 1 1/4" ric ok, left message 3/30/2005 2:34:45 PM