Inspections for the day of: Wednesday, March 30, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00743 FIR-Aging Inspection3/30/20053/30/20053/30/2005 12:00:00 AM NR
Project was on hold until general contractor returns at the first of April 3/30/2005 12:58:33 PM
MIS04-00325 MIS-Aging Inspection3/30/20053/30/20053/30/2005 12:00:00 AM NR
Per Keith at ###-#### items still need correcting. He will address immediately. 3/30/2005 2:58:30 PM
BLD04-01847 FIRE-Final Inspection3/25/20053/30/20053/30/2005 12:00:00 AMAPASS
Fire life safety finaled 3/30/2005 9:53:56 AM
FIR05-00131 INSP-Final Inspection3/25/20053/30/20053/30/2005 12:00:00 AMACANC
This si Grants Cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
BLD04-02239 FIRE-Final Inspection3/29/20053/30/20053/30/2005 12:00:00 AMAFAIL
###-#### The relocated smoke detector in the basement did not operate and according to Alarmco the fire alarm panel has not contacted the monitoring company since Monday the 28th of March. The building manintenance guy has been notified 3/30/2005 9:53:14 AM
BLD04-02330 FIRE-Final Inspection3/29/20053/30/20053/30/2005 12:00:00 AMAPASS
Fire life finaled 3/30/2005 10:13:29 AM
FIR05-00134 INSP-Final Inspection3/30/20053/30/20053/30/2005 12:00:00 AMPFAIL
Duct smoke detectors did not shut down hvac units. Need correct orfice in the inspectors test for proper testing. Provide knox key box per review note#10. Mount map at facp. Duct smoke detector zone is showing as vault alarm at the monitoring service. 3/30/2005 4:49:45 PM
FIR04-00769 INSP-Final Inspection3/30/20053/30/20053/30/2005 12:00:00 AMPFAIL
Some audio/visuals are mounted too high. See review note #11. Provide panel schedule in breaker box with lock for breaker. Provide signage on the fire riser door per review note #18. Provide as-builts per review note #1. 3/30/2005 2:52:27 PM
FIR04-00800 INSP-Final Inspection3/30/20053/30/20053/30/2005 12:00:00 AMPFAIL
Racks are blocking visuals. Need to resubmit accounting for obstructions to strobe coverage. 3/30/2005 1:01:00 PM
FIR04-00643 INSP-Supply line flush3/30/20053/30/20053/30/2005 12:00:00 AMPPASS
Underground supply line flush passed 3/30/2005 3:12:24 PM
BLD04-01997 FIRE-Final Inspection3/30/20053/30/20053/30/2005 12:00:00 AMPFAIL
Wrong plans on site. Floor plans do not match what is built
BLD05-00045 FIRE-Final Inspection3/30/20053/30/20053/30/2005 12:00:00 AMPCANC
Fire life safety finaled. Ray, the general contractor verified CFM rating is below 2000 CFM, therfore duct detectors are not required.