BLD06-00367
| FIRE-Final Inspection | 3/29/2006 | 3/30/2006 | 3/31/2006 8:11:18 AM | P | PASS |
|
|
Life safety finaled. The access controled egress doors had been disconnected from the fire alarm system. Mike re-connected them and they tested ok.
|
FIR06-00189
| INSP-Final Inspection | 3/29/2006 | 3/30/2006 | 3/31/2006 8:10:55 AM | P | PASS |
|
|
Fire alarm permit finaled. The access controled egress doors had been disconnected from the fire alarm system. Mike re-connected them and they tested ok.
|
FIR05-00596
| INSP-Sprinkler Rough-in/Hydro | 3/30/2006 | 3/30/2006 | 3/31/2006 7:11:18 AM | P | PASS |
|
|
Underground hydro test passed.
|
FIR06-00113
| INSP-Final Inspection | 3/30/2006 | 3/30/2006 | 3/30/2006 2:58:09 PM | P | FAIL |
|
|
Retaining straps missing in two locations
|
FIR06-00185
| INSP-Final Inspection | 3/30/2006 | 3/30/2006 | 3/30/2006 2:57:52 PM | P | FAIL |
|
|
Retaining straps missing in two locations
|
FIR05-00405
| INSP-Final Inspection | 3/30/2006 | 3/30/2006 | 3/30/2006 1:07:18 PM | P | FAIL |
|
|
Sprinkler heads are blocked by light fixtures. Heads need to be atleast 20" away from side of fixture. No other items inspected.
|
FIR05-00574
| INSP-Alarm Testing | 3/30/2006 | 3/30/2006 | 3/30/2006 1:06:09 PM | P | CANC |
|
|
To be rescheduled when the sprinklers are ready to be finaled
|
FIR06-00138
| INSP-Final Inspection | 3/30/2006 | 3/30/2006 | 3/30/2006 12:34:02 PM | P | FAIL |
|
|
Need to re-install the sprig up along the west exterior wall that was removed and install ceiling tile.
|
BLD06-00006
| FIRE-Final Inspection | 3/29/2006 | 3/30/2006 | 3/30/2006 10:33:17 AM | A | PASS |
|
|
permit finaled
|
BLD06-00596
| FIRE-Conference | 3/29/2006 | 3/30/2006 | 3/30/2006 10:14:31 AM | A | DONE |
|
|
Need approved door hardware installed on the south rear exit door. Exit signs and emergency lights are not required but contractor is installing anyway.
|
BLD05-02818
| FIRE-Final Inspection | 3/30/2006 | 3/30/2006 | 3/30/2006 9:11:32 AM | P | FAIL |
|
|
Provide fire extinguisher as per note #6, Provide approved hardware on the restroom doors(remove deadbolts), provide approved hardware on the west exterior door, provide approved hardware on the mechanical room door and fix the exit sign over the east exit.
|
BLD05-02817
| FIRE-Final Inspection | 3/30/2006 | 3/30/2006 | 3/30/2006 9:11:19 AM | P | FAIL |
|
|
Provide fire extinguisher as per note #6, Provide approved hardware on the restroom doors(remove deadbolts), provide approved hardware on the west exterior door, provide approved hardware on the mechanical room door and fix the exit sign over the east exit.
|
BLD05-03423
| FIRE-Final Inspection | 3/29/2006 | 3/30/2006 | 3/30/2006 9:11:00 AM | A | FAIL |
|
|
Provide fire extinguisher as per note #6, Provide approved hardware on the restroom doors(remove deadbolts), provide approved hardware on the west exterior door, provide approved hardware on the mechanical room door and fix the exit sign over the east exit.
|
FIR05-00174
| INSP-Final Inspection | 3/29/2006 | 3/30/2006 | 3/30/2006 12:00:00 AM | A | CANC |
|
|
Kenny; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong /// Cancel per Kenny (Treasure Valley Fire Protection) due to wrong address 3-30-06 eus
|
FIR05-00174
| INSP-Final Inspection | 3/29/2006 | 3/30/2006 | 3/30/2006 12:00:00 AM | A | CANC |
|
|
###-#### - kenny //// Cancel per Kenny (Treasure Valley Fire Protection) due to wrong address 3-30-06 eus
|
BLD05-03356
| FIRE-Final Inspection | 3/29/2006 | 3/30/2006 | 3/30/2006 12:00:00 AM | A | CANC |
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa /// Cancel per Matt (RA Schultz and Company) 3-30-06 eus
|