Inspections for the day of: Friday, March 30, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01062 Temporary Service3/30/20073/30/20073/30/2007 2:24:50 PMPFAIL
PLEASE INSPECT THE TEMPORARY POWER POLE LOCATED IN THE BACK CORNER OF THE PROPERTY. THANK YOU. ELECTRICIAN - KEVIN - ###-#### Phone #: ###-#### x0000 called
110.3(B) manufactures instructions milbank states 2 pole breakers , all breakers are disconnects only 6 allowed
ELE07-01063 Permanent Service3/30/20073/30/20073/30/2007 1:59:46 PMPPASS
brandon - call for key location; Phone #: ###-#### Internet Inspection Request from: Victoria Beall P/S U/G NEW OK
ELE07-01035 Permanent Service3/30/20073/30/20073/30/2007 1:41:19 PMPFAIL
JOe unit B; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
SEE NOTES TO PERMIT # ele07-01034 for info NOTE ONLY 1 METER WAS ALLOWED THIS IS A SINGLE FAM DWELLING NOT A DUPLEX SHALL GET WITH CITY FOR CHANGE
ELE07-01034 Permanent Service3/30/20073/30/20073/30/2007 1:38:48 PMPFAIL
JOe; Phone #: ###-#### Internet Inspection Request from: Stacie Backus see added t/s, corr. posted SINGLE FAMILY DWELLING ONLY 1 METER ALLOWED ON T/S BASIS, HAS 5 DAYS TO GET WITH CITY TO CHANGE FROM SINGLE FAM. TO DUPLEX OR POWER WILL BE DISCONNECTED RED TAG POSTED NOTE 1 METER ONLY
ELE07-01034 Temporary Service3/30/20073/30/20073/30/2007 1:34:11 PMPPART
JOe; Phone #: ###-#### Internet Inspection Request from: Stacie Backus t/s o/h rec. for
1 METER ON LY
ELE07-00070 Final3/30/20073/30/20073/30/2007 12:36:42 PMPFAIL
Greg pls call for access; Phone #: ###-#### Internet Inspection Request from: Stacie Backus 408.4 circuit directory be specific as gto purpose and use, 408.7 seak breaker KO with approved means called left ,message
ELE06-03221 Electrical Rough-In3/29/20073/30/20073/30/2007 10:01:06 AMAFAIL
bobby; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
corr. posted met owner partial correction only job not ready, and owner has done prior wiring without permit and covered without inspection , p/s needs upgrade, he has enclosed service entrance mast needs clearence over roof, panel in closet, 300.4 nail plates and 11/4", 314.20 boxes not flush with siding, 404.9(B) needs grd pigtails for switches, 250.148 grd all metal boxes, 110.3(B) install recess fixture for manufacture clearence from combustible material, BCC no violations retained COW
ELE07-00813 Final3/29/20073/30/20073/30/2007 8:28:12 AMACANC
audrey; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
see added r/i
ELE07-00813 Electrical Rough-In3/30/20073/30/20073/30/2007 8:27:42 AMAPASS
audrey; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
r/i ok corrections made
ELE07-01043 Final3/29/20073/30/20073/30/2007 8:05:22 AMAPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE07-01043 Electrical Rough-In3/30/20073/30/20073/30/2007 8:04:52 AMAPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
garage and u/g r/i ok