ELE07-01062
| Temporary Service | 3/30/2007 | 3/30/2007 | 3/30/2007 2:24:50 PM | P | FAIL |
|
|
PLEASE INSPECT THE TEMPORARY POWER POLE LOCATED IN THE BACK CORNER OF THE PROPERTY. THANK YOU. ELECTRICIAN - KEVIN - ###-#### Phone #: ###-#### x0000 called 110.3(B) manufactures instructions milbank states 2 pole breakers , all breakers are disconnects only 6 allowed
|
ELE07-01063
| Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 1:59:46 PM | P | PASS |
|
|
brandon - call for key location; Phone #: ###-#### Internet Inspection Request from: Victoria Beall P/S U/G NEW OK
|
ELE07-01035
| Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 1:41:19 PM | P | FAIL |
|
|
JOe unit B; Phone #: ###-#### Internet Inspection Request from: Stacie Backus SEE NOTES TO PERMIT # ele07-01034 for info NOTE ONLY 1 METER WAS ALLOWED THIS IS A SINGLE FAM DWELLING NOT A DUPLEX SHALL GET WITH CITY FOR CHANGE
|
ELE07-01034
| Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 1:38:48 PM | P | FAIL |
|
|
JOe; Phone #: ###-#### Internet Inspection Request from: Stacie Backus see added t/s, corr. posted SINGLE FAMILY DWELLING ONLY 1 METER ALLOWED ON T/S BASIS, HAS 5 DAYS TO GET WITH CITY TO CHANGE FROM SINGLE FAM. TO DUPLEX OR POWER WILL BE DISCONNECTED RED TAG POSTED NOTE 1 METER ONLY
|
ELE07-01034
| Temporary Service | 3/30/2007 | 3/30/2007 | 3/30/2007 1:34:11 PM | P | PART |
|
|
JOe; Phone #: ###-#### Internet Inspection Request from: Stacie Backus t/s o/h rec. for 1 METER ON LY
|
ELE07-00070
| Final | 3/30/2007 | 3/30/2007 | 3/30/2007 12:36:42 PM | P | FAIL |
|
|
Greg pls call for access; Phone #: ###-#### Internet Inspection Request from: Stacie Backus 408.4 circuit directory be specific as gto purpose and use, 408.7 seak breaker KO with approved means called left ,message
|
ELE06-03221
| Electrical Rough-In | 3/29/2007 | 3/30/2007 | 3/30/2007 10:01:06 AM | A | FAIL |
|
|
bobby; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. posted met owner partial correction only job not ready, and owner has done prior wiring without permit and covered without inspection , p/s needs upgrade, he has enclosed service entrance mast needs clearence over roof, panel in closet, 300.4 nail plates and 11/4", 314.20 boxes not flush with siding, 404.9(B) needs grd pigtails for switches, 250.148 grd all metal boxes, 110.3(B) install recess fixture for manufacture clearence from combustible material, BCC no violations retained COW
|
ELE07-00813
| Final | 3/29/2007 | 3/30/2007 | 3/30/2007 8:28:12 AM | A | CANC |
|
|
audrey; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see added r/i
|
ELE07-00813
| Electrical Rough-In | 3/30/2007 | 3/30/2007 | 3/30/2007 8:27:42 AM | A | PASS |
|
|
audrey; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i ok corrections made
|
ELE07-01043
| Final | 3/29/2007 | 3/30/2007 | 3/30/2007 8:05:22 AM | A | PASS |
|
|
darrell; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE07-01043
| Electrical Rough-In | 3/30/2007 | 3/30/2007 | 3/30/2007 8:04:52 AM | A | PASS |
|
|
darrell; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles garage and u/g r/i ok
|