ELE07-01001
| Final | 3/30/2007 | 3/30/2007 | 3/30/2007 4:18:14 PM | P | CANC |
|
|
Dave ###-#### called contr, wrong address, no work done at this site
|
ELE06-03427
| Final | 3/30/2007 | 3/30/2007 | 3/30/2007 3:57:43 PM | P | PART |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called contr, told to strap riser, check recpt operation by water heater, west side, sw recpt, n side trips gfci in other room, no power in front north wall, floor box cover not approved, since recpts flooded
|
ELE07-00920
| Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 2:47:29 PM | P | PASS |
|
|
Phone #: ###-#### p/s o/h n ok, u/g ok to cover, no time comp down
|
ELE07-00918
| Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 2:46:22 PM | P | PASS |
|
|
Phone #: ###-#### p/s o/h n ok, u/g ok to cover, no time comp down
|
ELE07-00917
| Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 2:45:29 PM | P | PASS |
|
|
Phone #: ###-#### p/s o/h n ok, u/g ok no time, comp down
|
ELE07-01007
| Rough-In Permanent Service | 3/30/2007 | 3/30/2007 | 3/30/2007 2:43:30 PM | P | PASS |
|
|
Jason Prior to a meter...preferrably before 2:00...if not by then call Anny @ ###-####.; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ric ok for u/g, p/s u/g n ok no time, computer down
|
ELE07-01031
| Temporary Service | 3/29/2007 | 3/30/2007 | 3/30/2007 11:50:48 AM | A | PASS |
|
|
Phone #: ###-#### t/s u/g n ok
|
ELE07-01044
| Temporary Service | 3/29/2007 | 3/30/2007 | 3/30/2007 9:45:47 AM | A | FAIL |
|
|
Phone #: ###-#### called, left corr notice, nec 230.24(B)(2) service drop conductors shall be min 12' over driveway
|
ELE06-04103
| Final | 3/29/2007 | 3/30/2007 | 3/30/2007 8:47:10 AM | A | PASS |
|
|
Code to get in is: 1234 enter. Please call Sean with problems or questions. Thanks. Phone #: ###-#### x0000 ok to final
|