Inspections for the day of: Friday, March 30, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01001 Final3/30/20073/30/20073/30/2007 4:18:14 PMPCANC
Dave ###-#### called contr, wrong address, no work done at this site
ELE06-03427 Final3/30/20073/30/20073/30/2007 3:57:43 PMPPART
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called contr, told to strap riser, check recpt operation by water heater, west side, sw recpt, n side trips gfci in other room, no power in front north wall, floor box cover not approved, since recpts flooded
ELE07-00920 Permanent Service3/30/20073/30/20073/30/2007 2:47:29 PMPPASS
Phone #: ###-#### p/s o/h n ok, u/g ok to cover, no time comp down
ELE07-00918 Permanent Service3/30/20073/30/20073/30/2007 2:46:22 PMPPASS
Phone #: ###-#### p/s o/h n ok, u/g ok to cover, no time comp down
ELE07-00917 Permanent Service3/30/20073/30/20073/30/2007 2:45:29 PMPPASS
Phone #: ###-#### p/s o/h n ok, u/g ok no time, comp down
ELE07-01007 Rough-In Permanent Service3/30/20073/30/20073/30/2007 2:43:30 PMPPASS
Jason Prior to a meter...preferrably before 2:00...if not by then call Anny @ ###-####.; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ric ok for u/g, p/s u/g n ok no time, computer down
ELE07-01031 Temporary Service3/29/20073/30/20073/30/2007 11:50:48 AMAPASS
Phone #: ###-#### t/s u/g n ok
ELE07-01044 Temporary Service3/29/20073/30/20073/30/2007 9:45:47 AMAFAIL
Phone #: ###-#### called, left corr notice, nec 230.24(B)(2) service drop conductors shall be min 12' over driveway
ELE06-04103 Final3/29/20073/30/20073/30/2007 8:47:10 AMAPASS
Code to get in is: 1234 enter. Please call Sean with problems or questions. Thanks. Phone #: ###-#### x0000 ok to final