Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00502 Permanent Service3/30/20093/30/20093/30/2009 4:29:01 PMPNR
paul - late this afternoon please Phone #: ###-#### talked to man at house, called paul left message no response back, job not no grd rods installed yet needs to GEC to u/g water pipe within 5ft, looks like the mast needs to be higner for 10ft clearence from grade to drip loop, and wires in mast not terminated at meter yet
ELE09-00507 Rough-In Permanent Service3/30/20093/30/20093/30/2009 3:57:40 PMPPASS
Need ok for Id Power re-connect. Randy''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s o/h rec. ok
ELE09-00509 Final3/30/20093/30/20093/30/2009 3:06:10 PMPPASS
jim Phone #: ###-#### ok card signed
ELE09-00509 Electrical Rough-In3/30/20093/30/20093/30/2009 3:05:49 PMPPASS
ok
ELE08-02740 Electrical Rough-In3/30/20093/30/20093/30/2009 2:20:14 PMPPASS
This is for more underground cover any time you get by Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig all parking lot u/g ok
ELE08-02167 Permanent Service3/27/20093/30/20093/30/2009 1:44:38 PMAPASS
andy Phone #: ###-#### p/s u/g new ok
ELE09-00503 Permanent Service3/26/20093/30/20093/30/2009 1:06:12 PMPCANC
Service upgrade,any questions call Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose
stopped at site picked up info from owner for investigation report on Riverside electric
ELE09-00161 Final3/30/20093/30/20093/30/2009 12:16:44 PMPPASS
marv - please call 1 hr prior so that he can meet you there Phone #: ###-#### ok card signed
ESC08-01022 General Inspection3/30/20093/30/20093/30/2009 12:16:22 PMPPASS
ok
ELE08-03015 ELE-Aging Inspection3/30/20093/30/20093/30/2009 11:42:30 AM PART
wsuc
ELE09-00503 Conference3/30/20093/30/20093/30/2009 10:33:31 AMADONE
met with with Allstate electric, investigation report for Riverside elect, hot tub wired without permit or inspections
ELE07-03432 Final3/30/20093/30/20093/30/2009 10:25:09 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called corrections not made
ESC08-00179 General Inspection3/30/20093/30/20093/30/2009 9:16:53 AMAPASS
ok
ELE08-02167 Permanent Service3/30/20093/30/20093/30/2009 9:07:58 AMAFAIL
andy Phone #: ###-#### met contr needs to bond CT can will stop back later