ELE09-00502
| Permanent Service | 3/30/2009 | 3/30/2009 | 3/30/2009 4:29:01 PM | P | NR |
|
|
paul - late this afternoon please Phone #: ###-#### talked to man at house, called paul left message no response back, job not no grd rods installed yet needs to GEC to u/g water pipe within 5ft, looks like the mast needs to be higner for 10ft clearence from grade to drip loop, and wires in mast not terminated at meter yet
|
ELE09-00507
| Rough-In Permanent Service | 3/30/2009 | 3/30/2009 | 3/30/2009 3:57:40 PM | P | PASS |
|
|
Need ok for Id Power re-connect. Randy''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s o/h rec. ok
|
ELE09-00509
| Final | 3/30/2009 | 3/30/2009 | 3/30/2009 3:06:10 PM | P | PASS |
|
|
jim Phone #: ###-#### ok card signed
|
ELE09-00509
| Electrical Rough-In | 3/30/2009 | 3/30/2009 | 3/30/2009 3:05:49 PM | P | PASS |
|
|
ok
|
ELE08-02740
| Electrical Rough-In | 3/30/2009 | 3/30/2009 | 3/30/2009 2:20:14 PM | P | PASS |
|
|
This is for more underground cover any time you get by Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig all parking lot u/g ok
|
ELE08-02167
| Permanent Service | 3/27/2009 | 3/30/2009 | 3/30/2009 1:44:38 PM | A | PASS |
|
|
andy Phone #: ###-#### p/s u/g new ok
|
ELE09-00503
| Permanent Service | 3/26/2009 | 3/30/2009 | 3/30/2009 1:06:12 PM | P | CANC |
|
|
Service upgrade,any questions call Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose stopped at site picked up info from owner for investigation report on Riverside electric
|
ELE09-00161
| Final | 3/30/2009 | 3/30/2009 | 3/30/2009 12:16:44 PM | P | PASS |
|
|
marv - please call 1 hr prior so that he can meet you there Phone #: ###-#### ok card signed
|
ESC08-01022
| General Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 12:16:22 PM | P | PASS |
|
|
ok
|
ELE08-03015
| ELE-Aging Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 11:42:30 AM | | PART |
|
|
wsuc
|
ELE09-00503
| Conference | 3/30/2009 | 3/30/2009 | 3/30/2009 10:33:31 AM | A | DONE |
|
|
met with with Allstate electric, investigation report for Riverside elect, hot tub wired without permit or inspections
|
ELE07-03432
| Final | 3/30/2009 | 3/30/2009 | 3/30/2009 10:25:09 AM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Monty Adkinson called corrections not made
|
ESC08-00179
| General Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 9:16:53 AM | A | PASS |
|
|
ok
|
ELE08-02167
| Permanent Service | 3/30/2009 | 3/30/2009 | 3/30/2009 9:07:58 AM | A | FAIL |
|
|
andy Phone #: ###-#### met contr needs to bond CT can will stop back later
|