FIR08-00255
| INSP-Final Inspection | 3/27/2009 | 3/27/2009 | | P | |
|
|
Contact Rafe Phone#: ###-####
|
FIR08-00766
| INSP-Supply line flush | 3/27/2009 | 3/30/2009 | 3/30/2009 3:55:35 PM | P | PART |
|
|
See initials on plans for the last riser supply lead-in flush completed today serving the main building.
|
FIR09-00183
| INSP-Final Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 3:50:33 PM | P | PASS |
|
|
Scope of permit work field verified for completion, permit finaled.
|
BLD09-00080
| FIRE-Conference | 3/30/2009 | 3/30/2009 | 3/30/2009 3:40:29 PM | P | DONE |
|
|
On site visit regarding fire life safety conditions required for Occ.
|
BLD09-00359
| FIRE-Conference | 3/27/2009 | 3/30/2009 | 3/30/2009 3:38:26 PM | P | DONE |
|
|
On site conference regarding door hardware at the new storefront.
|
FIR08-00766
| INSP-Sprinkler Rough-in | 3/30/2009 | 3/30/2009 | 3/30/2009 3:34:22 PM | P | FAIL |
|
|
Thrust blocks at two 45 ells in the supply line to the SE detatched building are not of sufficient size or location, field changes in pipe routes must be shown on approved plans.
|
FIR08-00480
| INSP-Final Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 3:30:45 PM | A | PASS |
|
|
Items on correction notice have been completed, final fire sprinkler inspection passed.
|
FIR09-00135
| INSP-Sprinkler Rough-in/Hydro | 3/30/2009 | 3/30/2009 | 3/30/2009 3:29:52 PM | A | PART |
|
|
Overhead fire sprinkler system modifications at the new tenant are approved for cover.
|
FIR08-00766
| INSP-Supply line flush | 3/27/2009 | 3/30/2009 | 3/30/2009 3:28:25 PM | A | PART |
|
|
UG fire supply line flush for two east side riser lead-ins completed okay.
|