FIR07-00745
| INSP-Conference | 3/26/2009 | 3/27/2009 | | P | |
|
|
Inspection follow up.
|
FIR09-00130
| INSP-Final Inspection | 3/27/2009 | 3/30/2009 | 3/30/2009 4:37:15 PM | P | FAIL |
|
|
No actual alarm testing was performed today but I did a walk through and found strobes overspaced and others blocked by walls, smoke detectors too close to supply air diffusers and the interconnection with the pre-action system had not been pretested and had problems. I marked the deficiency locations on the city approved plans.
|
FIR08-00778
| INSP-Final Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 4:34:43 PM | P | FAIL |
|
|
No testing could be completed today due to multiple problems with the pressure switches.
|
FIR09-00131
| INSP-Final Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 2:23:20 PM | P | PASS |
|
|
life safety passed.
|
BLD08-01127
| FIRE-Final Inspection | 3/29/2009 | 3/30/2009 | 3/30/2009 2:22:21 PM | A | PASS |
|
|
Life safety passed.
|
FIR08-00750
| INSP-Final Inspection | 3/27/2009 | 3/30/2009 | 3/30/2009 2:21:45 PM | A | PASS |
|
|
Permit finaled. The reporting to the central station had to be changed.
|
BLD09-00340
| FIRE-Final Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 12:11:02 PM | A | FAIL |
|
|
Provide panic/fire haredware on the two south facing exterior exit doors. Provide panic/fire hardware on the two exit doors from the conference room 103 and provide the correct door swing. These items have been addressed on the city approved plans.
|
BLD08-02385
| FIRE-Final Inspection | 3/30/2009 | 3/30/2009 | 3/30/2009 12:07:19 PM | A | PASS |
|
|
life safety passed
|
BLD08-02490
| FIRE-Final Inspection | 3/27/2009 | 3/30/2009 | 3/30/2009 12:00:38 PM | A | PASS |
|
|
life safety passed.
|