FIR10-00096
| INSP-Sprinkler Rough-in | 3/29/2010 | 3/30/2010 | 3/31/2010 8:12:34 AM | A | PART |
|
|
The piping rough-in in general is passed. Trapeze hangers are required for the new 3" supply main since all of its weight is hanging from a single Z purlin and the earthquake bracing needs to be anchored at the beams as discussed with Roy. The overhead hydro test failed since a visable leak was found at a pendant and the 3" supply main had not been included in the test.
|
BLD09-02283
| FIRE-Final Inspection | 3/29/2010 | 3/30/2010 | 3/30/2010 1:43:46 PM | A | PART |
|
|
life safety passed
|
FIR10-00003
| INSP-Final Inspection | 3/30/2010 | 3/30/2010 | 3/30/2010 1:38:56 PM | P | PASS |
|
|
permit finaled
|
BLD09-02299
| FIRE-Conference | 3/29/2010 | 3/30/2010 | 3/30/2010 12:57:13 PM | A | DONE |
|
|
I went over the life safety requirements which included the need for exit discharge lights, lever hardware on the new office door and mounting the front fire extinguisher at the cashiers counter.
|