FIR10-00202
| INSP-Final Inspection | 3/29/2011 | 3/30/2011 | 3/30/2011 3:19:19 PM | P | FAIL |
|
|
Need to finish up inspection of duct smoke detectors. Need to connect the existing smoke detectors in the Liebert units to the facp and test. Need updated as-builts showing all devices and their locations. One remote annunciator for a duct smoke detector was activated without testing.
|
FIR10-00072
| INSP-Final Inspection | 3/29/2011 | 3/30/2011 | 3/30/2011 2:54:45 PM | A | PASS |
|
|
permit finaled
|
FIR10-00513
| INSP-Sprinkler Rough-in/Hydro | 3/30/2011 | 3/30/2011 | 3/30/2011 2:38:49 PM | P | PASS |
|
|
hydro test passed except for the FDC piping which was not put under the test.
|
BLD11-00381
| FIRE-Final Inspection | 3/30/2011 | 3/30/2011 | 3/30/2011 2:36:06 PM | P | PASS |
|
|
life safety passed.
|
FIR10-00514
| INSP-Sprinkler Rough-in/Hydro | 3/29/2011 | 3/30/2011 | 3/30/2011 2:17:19 PM | P | CANC |
|
|
Wrong permit/building called in for inspection.
|
FIR09-00190
| INSP-Final Inspection | 3/29/2011 | 3/30/2011 | 3/30/2011 11:30:19 AM | P | PASS |
|
|
Permit finaled
|
BLD11-00464
| FIRE-Final Inspection | 3/28/2011 | 3/30/2011 | 3/30/2011 10:10:58 AM | A | PASS |
|
|
Life safety passed.
|
BLD11-00506
| FIRE-Final Inspection | 3/29/2011 | 3/30/2011 | 3/30/2011 9:01:00 AM | A | PASS |
|
|
life safety passed. One fire extinguisher is missing its inspection tag. The manager is going to contact the contrator and get a replacement tag. Also on electrical junction box in the back room is missing a cover which is going to be replaved by the manager.
|
BLD10-01875
| FIRE-Final Inspection | 3/29/2011 | 3/30/2011 | 3/30/2011 8:59:09 AM | A | PART |
|
|
Phase II life safety passed. Two exit signs repaired while I waited. Also there are issues with the operation of the elevator recall. See the project related fire alarm permit for information.
|
FIR11-00067
| INSP-Final Inspection | 3/28/2011 | 3/30/2011 | 3/29/2011 3:13:18 PM | A | CANC |
|
|
Morgan with Protex is the contact. Please call him 30 min prior to inspection at ###-####. Protex office no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|