ELE11-01656
| ELE-Aging Inspection | 3/30/2012 | 3/30/2012 | 3/30/2012 4:19:44 PM | | DONE |
|
|
waiting for contractor to call to final
|
ELE12-00572
| Electrical Rough-In | 3/30/2012 | 3/30/2012 | 3/30/2012 2:17:28 PM | P | PASS |
|
|
Underground inspection Phone #: ###-#### >> Inspection requested via web by Bryan Atkins ok cover u/g north side building only
|
ELE12-00544
| Final | 3/29/2012 | 3/30/2012 | 3/30/2012 1:52:32 PM | P | PASS |
|
|
work is done repairs made j boxes in attic its ok someone will be working there fromm 11 till 6 paul i belive is his name Phone #: ###-#### >> Inspection requested via web by dennis mcneely ok final
|
ELE12-00653
| Final | 3/30/2012 | 3/30/2012 | 3/30/2012 1:12:39 PM | P | PASS |
|
|
jeff creek Phone #: ###-#### >> Inspection requested via web by Andrea Creek ok final
|
ELE12-00447
| Final | 3/30/2012 | 3/30/2012 | 3/30/2012 12:26:26 PM | P | PASS |
|
|
contact on site SID ###-#### Phone #: ###-#### >> Inspection requested via web by JENNY EMEL ok final, signed card
|
ELE12-00010
| Final | 3/29/2012 | 3/30/2012 | 3/30/2012 10:24:37 AM | A | FAIL |
|
|
marie or ###-#### Phone #: ###-#### met owner, shall provide dead front for panel and circuit directory, shall check for open ground in bedroom, check flex for water heater and pump, add gfci in bath, service was reconnected, can sticker at final, grounding ok, rest ok
|
ELE12-00102
| Final | 3/29/2012 | 3/30/2012 | 3/30/2012 9:41:04 AM | A | PASS |
|
|
requsting final inspection of electrical work for the bulk ammonia system. Phone #: ###-#### >> Inspection requested via web by Steve Moss ok final
|
ELE12-00189
| Final | 3/29/2012 | 3/30/2012 | 3/30/2012 8:08:29 AM | A | PASS |
|
|
Someone will be there. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan ok final
|