Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-00881 FIRE-Final Inspection3/30/20153/30/20153/31/2015 7:55:26 AMPPASS
Life safety passed. Provide address before building inspection and per plan review the emergency lighting is not required.
FIR14-00894 INSP-Sprinkler Rough-in3/27/20153/30/20153/30/2015 3:25:14 PMAPASS
See the city approved plans for piping that is ok to cover above hard lids.
FIR15-00161 INSP-Final Inspection3/26/20153/30/20153/30/2015 12:07:54 PMAPASS
Permit finaled
FIR15-00096 INSP-Sprinkler Rough-in3/27/20153/30/20153/30/2015 10:34:04 AMAPART
Inspection was for east wing of the 2nd floor. See the city approved plans for locations marked in red and dated with todays date. I noted one overspaced head that can be verified at final and two locations where the cpvc piping may be exceeding maximum flex. Many dummy drops are installed and no actual rc's or pendants and in these locations the dummy drop is very close to a wall.Rooms are ok to cover as marked (noted above). I spoke to the General Contractor about the fire stopping in the vertical chases and needing access to verifiy the fire stopping. He is going to try for a variance due to the fact he is building the vertical chases to meet 2 Hour construction.
BLD15-00825 FIRE-Final Inspection3/27/20153/30/20153/30/2015 10:10:35 AMAPASS
life safety passed