Inspections for the day of: Wednesday, March 30, 2016.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF16-00019 INSP-Sprinkler Rough-in3/29/20163/30/20163/30/2016 2:35:59 PMPPASS
Underground pipe ok to cover. Depth and thrust blocks completed satisfactory.
NAF15-00042 INSP-Sprinkler Rough-in3/29/20163/30/20163/30/2016 2:34:04 PMPNR
Under ground cover not ready, rescheduled for next day.
NAF16-00022 INSP-Final3/28/20163/30/20163/30/2016 11:35:28 AMAFAIL
The following items to be corrected:
-Back door has surface mounted bolt lock to be removed. It is allowed to be replaced with a keyed deadbolt. ("door to be unlocked" signs already posted)
-Emergency backup light at front entrance to be repaired or removed. Occupancy is less that 49 so it is not required.
- Advised owner that the aisle to the back door needs to be kept clear or storage.