MEC17-01130
| Final | 3/29/2017 | 3/30/2017 | 3/30/2017 3:54:04 PM | P | PASS |
|
|
Please have inspector call installer Aaron when in route to home, request late afternoon. ###-#### Inspection requested via web by Carolyn Rudd
|
MEC17-01142
| Rough-in | 3/30/2017 | 3/30/2017 | 3/30/2017 3:02:20 PM | P | PASS |
|
|
Dave Phone #: ###-####-including flue underground piping- manual J needs resubmitted for equipment before final-
|
MEC17-01142
| Pressure Test | 3/30/2017 | 3/30/2017 | 3/30/2017 2:56:40 PM | P | PASS |
|
|
Dave Phone #: ###-####- 20lb gas and 5lb flue pass
|
MEC16-04971
| Rough-in | 3/30/2017 | 3/30/2017 | 3/30/2017 1:53:09 PM | P | PART |
|
|
Ceiling cover inspection. Contact Derek ###-#### Phone #: ###-#### Inspection requested via web by Dan Flaherty- need to finish support and armor flex on linsets in various parts of building- register need covered for green building code- dryer exhauster needs support- ok for cover after these items have been addressed
|
MEC16-03968
| Mec-Aging Inspection | 3/30/2017 | 3/30/2017 | 3/30/2017 11:37:01 AM | | NH |
|
|
work in progress- called homeowner and left message to call me back
|
MEC17-00903
| Rough-in | 3/29/2017 | 3/30/2017 | 3/30/2017 11:04:12 AM | A | PART |
|
|
Requesting a partial rough in inspection tomorrow morning. Contact is Jason ###-####. Phone #: ###-#### Inspection requested via web by Kathy Youngkin- area ACAMS and office space/conference room seal ok- ok to insulate duct
|
MEC16-05525
| Final | 3/29/2017 | 3/30/2017 | 3/30/2017 10:34:12 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer- air balance report is low, need more air into house- need drip leg on gas line at furnace- cant get to outdoor unit for all-excavation work going on- big holes around it - momentum says huge hole on supply plenum need to look at report-need approved manual J onsite for inspection
|
MEC17-00154
| Final | 3/29/2017 | 3/30/2017 | 3/30/2017 10:11:34 AM | A | FAIL |
|
|
Inspection requested via web by Matthew Grant- need approved manual J onsite- manual J shows bryant equipment and carrier is installed-need 8" round or 12x4 boot in ceiling for combustion air in furnace/water heater closet- need air balance report to do final inspection
|