Inspections for the day of: Friday, March 30, 2018.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00733 INSP-Final Inspection3/29/20183/30/20183/30/2018 3:08:27 PMAFAIL
There were issues with the interconnection of the pressure switches and tamper switches. No actual testing was performed.

Zach Phone #: ###-####
FIR17-00541 INSP-Final Inspection3/29/20183/30/20183/30/2018 3:07:16 PMACANC
Unable to test the system due to fire alarm interface issues.


RICK FRY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
BLD16-04428 FIRE-Final Inspection3/29/20183/30/20183/30/2018 3:05:04 PMAPASS
Life safety passed as per activity comments no sign off required. Fire hydrants and fire dept access reviewed under the Grading permit

Phone #: ###-#### Inspection requested via web by Chris Palmer
FIR17-00309 INSP-Sprinkler Rough-in/Hydro3/29/20183/30/20183/30/2018 3:04:08 PMAPASS
Permit finaled. Overhead hydro test passed. Placards are on order.

Todd Ketterling is the contact for this hydro. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-04103 FIRE-Final Inspection3/29/20183/30/20183/30/2018 8:19:20 AMAPASS
life safety passed


Please see request for fire sprinkler final to save on two trips to same site. Phone #: ###-#### Inspection requested via web by Mark Steen
BLD17-04635 FIRE-Final Inspection3/29/20183/30/20183/30/2018 7:43:53 AMAPASS
Life safety passed

Mike-please call 30 minutes prior to meet for access Phone #: ###-####