Inspections for the day of: Monday, March 30, 2020.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTell Riley
TitleBLD-COM/RES INSPECTOR
Phone #830-2752
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-02866 BLD-Final3/30/20203/30/20203/30/2020 3:03:46 PMPDONE
chace Phone #: ###-####
BLD19-02866 DOC - Permit Finaled3/30/20203/30/20203/30/2020 3:03:37 PMPPASS
work appears to be complete per the scope of work in the description
BLD19-03440 BLD-Energy code compliance3/30/20203/30/20203/30/2020 2:12:40 PMPPASS
Rick Phone #: ###-####//corrections made//
BLD19-04204 BLD-Energy code compliance3/30/20203/30/20203/30/2020 12:44:17 PMPPASS
Thanks Phone #: ###-#### Inspection requested via web by bryan murdoch//windows ok//walls ok// ceiling has R38 batts visible, person onsite said r11 was installed above the r38//check insulation certificate at final for r49 in attic//crawl space insulation has not been insulated//
BLD19-03229 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:20:52 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk////see corrections prior to any cover approval//need letter from engineer//ok to insulate//
BLD19-03253 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:20:29 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk////see corrections prior to any cover approval//need letter from engineer//ok to insulate//
BLD19-03247 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:20:00 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk//see corrections prior to any cover approval//need letter from engineer//ok to insulate//
BLD19-03248 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:19:30 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk//see corrections prior to any cover approval//need letter from engineer//ok to insulate//
BLD19-03249 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:19:14 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk////see corrections prior to any cover approval//need letter from engineer//ok to insulate//
BLD19-03250 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:18:55 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk////see corrections prior to any cover approval//need letter from engineer//ok to insulate//
BLD19-03251 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:18:36 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk////see corrections prior to any cover approval//need letter from engineer//ok to insulate//
BLD19-03252 BLD-Framing/Rough-in3/29/20203/30/20203/30/2020 11:18:10 AMAPART
Phone #: ###-#### Inspection requested via web by Carl Funk//see corrections prior to any cover approval//need letter from engineer//ok to insulate//