ELE02-03818
| Electrical Rough-In | 3/28/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | A | FAIL |
|
|
jim ###-#### 300.4 nail plates and 11/4 for MC, and insulation installed before inspection ,on some walls met with contractor 3/31/2003 9:45:14 AM
|
ELE03-00867
| Rough-In Permanent Service | 3/31/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | A | PASS |
|
|
NOW IS IN FOR WEST CHANDRA LN-RESEND PER JACK this east of Eagleson, just south of Overland r/i ok p/s u/g new ok 3/31/2003 9:03:41 AM
|
ELE03-00867
| Rough-In Permanent Service | 3/24/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | A | CANC |
|
|
###-####--PER JACK FRANK CANCEL THIS ONE THEN RESEND BACK FOR AM
|
ELE02-03965
| Final | 3/28/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 3/28/2003 at 7:26:47 AM. Contact: ###-####. met contractor needs to install wire and ID it for boxes above grid, bushings for fire alarm cables at 4 sq boxes and wiring for emergency ballast shall be enclosed
3/31/2003 12:40:48 PM
|
ELE02-03818
| Electrical Rough-In | 3/31/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | PART |
|
|
###-#### r/i ok for walls only main bar, patio bar, rest rms, office , and game rm 3/31/2003 1:56:48 PM
|
ELE03-00938
| Rough-In Permanent Service | 3/31/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | FAIL |
|
|
###-#### jerry cor. posted called left message, 300.4 (A)(1),(D). 300.14 short grd wires, 250.24 (A), and (A)(5) terminate at service not sub panel and isolate grd and neutrals at sub panels 3/31/2003 2:57:11 PM
|
ELE03-00477
| Final | 3/31/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | FAIL |
|
|
cor. posted called 600.5(C)(3) and 410.15(B) shall weld in nipple install box grd it and install raceways inside of sign is open
|