Inspections for the day of: Monday, March 31, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02697 FIRE-Final Inspection3/28/20033/31/20033/31/2003 12:00:00 AMAPASS
JACK; Phone #: ###-#### Fire life safety finaled 3/31/2003 10:34:29 AM
FIR02-00478 INSP-Final Inspection3/27/20033/31/20033/31/2003 12:00:00 AMAFAIL
MIKE 8AM INSPECTION; Phone #: ###-#### test all recall functions for the elevator including all heat and smoke detectors, provide smoke for all fire smoke dampers per review note #6, provide duct smoke detectors on the supply side of the HVAC units or get permission from the boise fire dept. to leave them on the return side, provide a map of system 3/31/2003 9:40:44 AM
FIR03-00036 INSP-Final Inspection3/27/20033/31/20033/31/2003 12:00:00 AMACANC
MIKE 8AM INSPECTION; Phone #: ###-#### Could not do the inspection because there was no access to the inspectors test 3/31/2003 9:55:37 AM
FIR02-00372 INSP-Final Inspection3/28/20033/31/20033/31/2003 12:00:00 AMPFAIL
This is Patrick Cell; Phone #: ###-#### This inspection turned into a conference. The a/v's work but devices need to be added on a mezzanine area and in multiple offices. Also the audio does not meet the minimum 75 db requirements in all areas. The fire sprinkler devices have been tested but the signals did not come in right. All pull stations worked. No other devices tested. 3/31/2003 3:19:21 PM
BLD02-02313 FIRE-Final Inspection3/31/20033/31/20033/31/2003 12:00:00 AMPFAIL
Provide additional smoke detectors in the adjoining rooms and test all smoke detectors, provide curb painting, adjust and check all self closing entry exit doors 3/31/2003 3:31:03 PM
BLD02-03027 FIRE-Final Inspection3/31/20033/31/20033/31/2003 12:00:00 AMPPASS
Fire life/safety finaled 3/31/2003 4:12:31 PM
BLD03-00296 FIRE-Final Inspection3/31/20033/31/20033/31/2003 12:00:00 AMPPASS
Fire life safety finaled. Owner to reduce the height of the plastic slides to less than 6' 3/31/2003 10:58:49 AM