BLD02-02697
| FIRE-Final Inspection | 3/28/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | A | PASS |
|
|
JACK; Phone #: ###-#### Fire life safety finaled 3/31/2003 10:34:29 AM
|
FIR02-00478
| INSP-Final Inspection | 3/27/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | A | FAIL |
|
|
MIKE 8AM INSPECTION; Phone #: ###-#### test all recall functions for the elevator including all heat and smoke detectors, provide smoke for all fire smoke dampers per review note #6, provide duct smoke detectors on the supply side of the HVAC units or get permission from the boise fire dept. to leave them on the return side, provide a map of system 3/31/2003 9:40:44 AM
|
FIR03-00036
| INSP-Final Inspection | 3/27/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | A | CANC |
|
|
MIKE 8AM INSPECTION; Phone #: ###-#### Could not do the inspection because there was no access to the inspectors test 3/31/2003 9:55:37 AM
|
FIR02-00372
| INSP-Final Inspection | 3/28/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | FAIL |
|
|
This is Patrick Cell; Phone #: ###-#### This inspection turned into a conference. The a/v's work but devices need to be added on a mezzanine area and in multiple offices. Also the audio does not meet the minimum 75 db requirements in all areas. The fire sprinkler devices have been tested but the signals did not come in right. All pull stations worked. No other devices tested. 3/31/2003 3:19:21 PM
|
BLD02-02313
| FIRE-Final Inspection | 3/31/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | FAIL |
|
|
Provide additional smoke detectors in the adjoining rooms and test all smoke detectors, provide curb painting, adjust and check all self closing entry exit doors 3/31/2003 3:31:03 PM
|
BLD02-03027
| FIRE-Final Inspection | 3/31/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | PASS |
|
|
Fire life/safety finaled 3/31/2003 4:12:31 PM
|
BLD03-00296
| FIRE-Final Inspection | 3/31/2003 | 3/31/2003 | 3/31/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled. Owner to reduce the height of the plastic slides to less than 6' 3/31/2003 10:58:49 AM
|