Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00883 Temporary Service3/30/20043/31/20043/31/2004 12:00:00 AMAFAIL
###-#### doug please call for access
connect GEC To neutral and install main bonding jumper 3/31/2004 8:55:33 AM
ELE04-00885 Final3/30/20043/31/20043/31/2004 12:00:00 AMAPASS
there is a map in Jim Schmer's office if needed///jean keith ###-####
P/S U/G N Ok 3/31/2004 9:58:35 AM
ELE04-00889 Conference3/30/20043/31/20043/31/2004 12:00:00 AMAPART
WAYNE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ELE04-00011 Final3/30/20043/31/20043/31/2004 12:00:00 AMAFAIL
TIM; Phone #: ###-#### Internet Inspection Request from: Darla Downs
Recep under sink for lights in guest bathroom on 1st floor shall be GFCI protected per 210.8 3/31/2004 9:27:07 AM
ELE04-00417 Electrical Rough-In3/30/20043/31/20043/31/2004 12:00:00 AMAPART
above ceiling inspection please for the 6th floor only///george; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
outside perimerer ceiling ok on 6th floor
anop 3/31/2004 3:29:31 PM
ELE04-00874 Electrical Rough-In3/30/20043/31/20043/31/2004 12:00:00 AMAFAIL
JEAN ENTRY SOFFIT; Phone #: ###-#### Internet Inspection Request from: Darla Downs

Flex feeding lights has over 360 deg of bend.

Plastic boxes in the entry way are listed only for nonmetallic wiring methods.

Romex is not permitted. In entry ceiling. 3/31/2004 10:38:02 AM
ELE03-03953 Electrical Rough-In3/31/20043/31/20043/31/2004 12:00:00 AMPPART
late afternoon please///HP ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
underground is ok
corrections not finished COW 3/31/2004 4:29:09 PM
ELE03-03598 Final3/31/20043/31/20043/31/2004 12:00:00 AMPPASS
###-####. Scheduled by a contractor via Hello! on 3/31/2004 at 8:34:26 AM. Contact: ###-####. 3/31/2004 1:03:09 PM
ELE03-02132 Final3/31/20043/31/20043/31/2004 12:00:00 AMPPASS
###-####. Scheduled by a contractor via Hello! on 3/31/2004 at 8:43:55 AM. Contact: ###-####. 3/31/2004 1:03:22 PM
ELE04-00883 Temporary Service3/31/20043/31/20043/31/2004 12:00:00 AMPPASS
T/S U/G Ok