Inspections for the day of: Wednesday, March 31, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00037 INSP-Final Inspection3/30/20043/31/20043/31/2004 12:00:00 AMAPART
Inspection was for area 1-2. This area finaled 3/31/2004 10:41:57 AM
BLD03-02762 FIRE-Final Inspection3/30/20043/31/20043/31/2004 12:00:00 AMAPART
Fire life safety given a temporary occupancy until the remote alarm led is repaired. Hvac units do shut down upon smoke detection 3/31/2004 1:55:51 PM
FIR03-00780 INSP-Supply line flush3/31/20043/31/20043/31/2004 12:00:00 AMPPASS
above ground wet system and underground hydro test ok. Flush of the underground supply line flush is ok 3/31/2004 4:13:12 PM 3/31/2004 4:13:36 PM
BLD04-00152 FIRE-Final Inspection3/30/20043/31/20043/31/2004 12:00:00 AMPPASS
fire life safety and fire sprinklers finaled. No modifications were performed on the fire alarm/smoke control in this tenant per contractor and the scope of work 3/31/2004 1:57:15 PM
FIR04-00160 INSP-Sprinkler Rough-in/Hydro3/30/20043/31/20043/31/2004 12:00:00 AMPFAIL
This permit should be attached to BLD04-00054. The eight sprinkler pendants for this permit are blocked by glass box like obstructions. I went over it with the sprinkler contractor. Resubmittals required 3/31/2004 3:36:42 PM