FIR04-00037
| INSP-Final Inspection | 3/30/2004 | 3/31/2004 | 3/31/2004 12:00:00 AM | A | PART |
|
|
Inspection was for area 1-2. This area finaled 3/31/2004 10:41:57 AM
|
BLD03-02762
| FIRE-Final Inspection | 3/30/2004 | 3/31/2004 | 3/31/2004 12:00:00 AM | A | PART |
|
|
Fire life safety given a temporary occupancy until the remote alarm led is repaired. Hvac units do shut down upon smoke detection 3/31/2004 1:55:51 PM
|
FIR03-00780
| INSP-Supply line flush | 3/31/2004 | 3/31/2004 | 3/31/2004 12:00:00 AM | P | PASS |
|
|
above ground wet system and underground hydro test ok. Flush of the underground supply line flush is ok 3/31/2004 4:13:12 PM 3/31/2004 4:13:36 PM
|
BLD04-00152
| FIRE-Final Inspection | 3/30/2004 | 3/31/2004 | 3/31/2004 12:00:00 AM | P | PASS |
|
|
fire life safety and fire sprinklers finaled. No modifications were performed on the fire alarm/smoke control in this tenant per contractor and the scope of work 3/31/2004 1:57:15 PM
|
FIR04-00160
| INSP-Sprinkler Rough-in/Hydro | 3/30/2004 | 3/31/2004 | 3/31/2004 12:00:00 AM | P | FAIL |
|
|
This permit should be attached to BLD04-00054. The eight sprinkler pendants for this permit are blocked by glass box like obstructions. I went over it with the sprinkler contractor. Resubmittals required 3/31/2004 3:36:42 PM
|