ELE05-04600
| Electrical Rough-In | 3/31/2006 | 3/31/2006 | 3/31/2006 4:16:04 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 3/31/2006 at 8:02:59 AM. called contractor called in wrong permit for inspection , he will reschedule for 04-03-06 with correct permit number
|
ELE06-00983
| Final | 3/31/2006 | 3/31/2006 | 3/31/2006 3:45:26 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ok
|
ELE05-04498
| Rough-In Permanent Service | 3/31/2006 | 3/31/2006 | 3/31/2006 3:29:40 PM | P | FAIL |
|
|
Address will be painted on side this morning; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr. called 210.25 needs common area panel and branch circuits for stair lighting, 110.3(A&B) min. amps for electric heat 52 amp they only have 50, 300.4 nail plates and 11/4" everywhere, 334.30 cables stapled on egde, 220.84 calcs for p/s and feeders too apartments all electric also need plans at each building
|
ELE06-01079
| Electrical Rough-In | 3/31/2006 | 3/31/2006 | 3/31/2006 2:27:34 PM | P | PART |
|
|
Brad ###-#### -- ok per Jack Frank as stated by Kerri (Idaho Electric Contracting) 3-31-06 eus soffit lights ok
|
ELE05-04229
| Final | 3/31/2006 | 3/31/2006 | 3/31/2006 1:55:16 PM | P | PASS |
|
|
Dennis; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok card signed
|
ELE06-00715
| Final | 3/31/2006 | 3/31/2006 | 3/31/2006 1:03:50 PM | P | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange house tested ok garage not ready called
|
ELE06-00716
| Final | 3/31/2006 | 3/31/2006 | 3/31/2006 1:03:08 PM | P | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange house tested ok garage not ready called
|
ELE06-01054
| Rough-In Permanent Service | 3/31/2006 | 3/31/2006 | 3/31/2006 12:47:24 PM | P | FAIL |
|
|
Tim -- call 1st before insp; reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong see added reinspection fee due for corr. info
|
ELE06-01102
| Temporary Service | 3/31/2006 | 3/31/2006 | 3/31/2006 10:34:28 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g new ok
|
ELE06-00843
| Electrical Rough-In | 3/31/2006 | 3/31/2006 | 3/31/2006 10:34:00 AM | P | PART |
|
|
underground conduit-for the shop- vivian; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
|
ELE05-04668
| ELE-Aging Inspection | 3/31/2006 | 3/31/2006 | 3/31/2006 9:55:36 AM | | PASS |
|
|
|
ELE05-04668
| Final | 3/31/2006 | 3/31/2006 | 3/31/2006 9:55:18 AM | A | PASS |
|
|
sign ok ul listing
|
ELE06-01081
| Final | 3/30/2006 | 3/31/2006 | 3/31/2006 9:22:50 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty corr. called 100.3(A&B) min max overcurrent protection per manufactures specs,408.4 label panel, 314.15(A) use listed r/t fittings
|
ELE05-04498
| Rough-In Permanent Service | 3/30/2006 | 3/31/2006 | 3/31/2006 8:23:49 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called no address on building and the site is a mud and water hole
|
ELE06-01054
| Rough-In Permanent Service | 3/30/2006 | 3/31/2006 | 3/31/2006 12:00:00 AM | A | CANC |
|
|
Tim -- reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong /// Cancel per Tim (BenCorp) and reschedule for 3-31 PM 3-31-06 eus
|
ELE05-04628
| Final | 3/29/2006 | 3/31/2006 | 3/30/2006 8:23:58 AM | A | CANC |
|
|
robert--call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie///cancelled per Robert, will call back to reschedule 3/30/06 LEG// Inspection cancelled from web by: Letitia Mesa
|