ELE05-03809
| Final | 3/31/2006 | 3/31/2006 | 3/31/2006 4:41:29 PM | P | PASS |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE06-00790
| Electrical Rough-In | 3/31/2006 | 3/31/2006 | 3/31/2006 3:59:40 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer u/g ok to use, ceiling not ready, will recall
|
ELE05-04669
| ELE-Aging Inspection | 3/31/2006 | 3/31/2006 | 3/31/2006 3:38:14 PM | | DONE |
|
|
could not find sign, looks like suc
|
ELE05-04513
| Electrical Rough-In | 3/31/2006 | 3/31/2006 | 3/31/2006 2:52:01 PM | P | FAIL |
|
|
Mike -- underground conduit; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong 300.5 nonmetallic raceway shall be 24" deep under drive and 18" by fence, called contr, left message
|
ELE06-00248
| Final | 3/31/2006 | 3/31/2006 | 3/31/2006 2:08:11 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/31/2006 at 7:31:49 AM. Contact: ###-####. called, left message, 314.15(A) emt connectors and couplings shall be listed for wet locations
|
ELE06-01103
| Rough-In Permanent Service | 3/31/2006 | 3/31/2006 | 3/31/2006 1:13:58 PM | P | PASS |
|
|
darrell ###-#### upstairs to be unfinished, feeder out bottom of panel, ric ok, p/s u/g n ok
|
ELE06-00148
| Final | 3/30/2006 | 3/31/2006 | 3/31/2006 11:33:12 AM | A | PASS |
|
|
Internet Inspection Request from: Ryan Christensen ok to final
|
ELE06-01070
| Rough-In Permanent Service | 3/30/2006 | 3/31/2006 | 3/31/2006 10:34:53 AM | A | PASS |
|
|
Bob, please call me if you have any problems. Thanks, Shane.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil ric ok, p/s u/g n ok
|
ELE06-01100
| Rough-In Permanent Service | 3/30/2006 | 3/31/2006 | 3/31/2006 9:13:41 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called left message, BCC all make-up shall be done, 210.52 (A)(2) receptacles shall be added in any wall space over 2' in width, 110.12(C) there shall be no broken boxes, 300.4(A) edge of holes shall be 1 1/4" from edge of framing member, 725.55(A) class 2&3 cables shall not be run with class 1 conductors
|
ELE06-01075
| Final | 3/30/2006 | 3/31/2006 | 3/31/2006 8:24:53 AM | A | PASS |
|
|
please contact Julian, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters see p/s, ok to final
|
ELE06-01075
| Permanent Service | 3/31/2006 | 3/31/2006 | 3/31/2006 8:24:15 AM | P | PASS |
|
|
please contact Julian, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters corr made, p/s exst meter, o/h ok
|