Inspections for the day of: Friday, March 31, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03809 Final3/31/20063/31/20063/31/2006 4:41:29 PMPPASS
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE06-00790 Electrical Rough-In3/31/20063/31/20063/31/2006 3:59:40 PMPPART
Phone #: ###-#### Internet Inspection Request from: Heather Packer u/g ok to use, ceiling not ready, will recall
ELE05-04669 ELE-Aging Inspection3/31/20063/31/20063/31/2006 3:38:14 PM DONE
could not find sign, looks like suc
ELE05-04513 Electrical Rough-In3/31/20063/31/20063/31/2006 2:52:01 PMPFAIL
Mike -- underground conduit; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong 300.5 nonmetallic raceway shall be 24" deep under drive and 18" by fence, called contr, left message
ELE06-00248 Final3/31/20063/31/20063/31/2006 2:08:11 PMPFAIL
Scheduled by a contractor via Hello! on 3/31/2006 at 7:31:49 AM. Contact: ###-####. called, left message, 314.15(A) emt connectors and couplings shall be listed for wet locations
ELE06-01103 Rough-In Permanent Service3/31/20063/31/20063/31/2006 1:13:58 PMPPASS
darrell ###-#### upstairs to be unfinished, feeder out bottom of panel, ric ok, p/s u/g n ok
ELE06-00148 Final3/30/20063/31/20063/31/2006 11:33:12 AMAPASS
Internet Inspection Request from: Ryan Christensen ok to final
ELE06-01070 Rough-In Permanent Service3/30/20063/31/20063/31/2006 10:34:53 AMAPASS
Bob, please call me if you have any problems. Thanks, Shane.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil ric ok, p/s u/g n ok
ELE06-01100 Rough-In Permanent Service3/30/20063/31/20063/31/2006 9:13:41 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called left message, BCC all make-up shall be done, 210.52 (A)(2) receptacles shall be added in any wall space over 2' in width, 110.12(C) there shall be no broken boxes, 300.4(A) edge of holes shall be 1 1/4" from edge of framing member, 725.55(A) class 2&3 cables shall not be run with class 1 conductors
ELE06-01075 Final3/30/20063/31/20063/31/2006 8:24:53 AMAPASS
please contact Julian, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters see p/s, ok to final
ELE06-01075 Permanent Service3/31/20063/31/20063/31/2006 8:24:15 AMPPASS
please contact Julian, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters corr made, p/s exst meter, o/h ok