Inspections for the day of: Friday, March 31, 2006.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-03356 FIRE-Final Inspection3/31/20063/31/20063/31/2006 3:49:19 PMPPASS
Life safety passed.
FIR06-00185 INSP-Final Inspection3/31/20063/31/20063/31/2006 3:40:16 PMPPASS
Permit finaled
BLD05-00978 FIRE-Final Inspection3/31/20063/31/20063/31/2006 3:39:58 PMPFAIL
Need to final fire alarm permit and provide corrections as marked on the fire dept. plan review comments.
FIR05-00898 INSP-Final Inspection3/30/20063/31/20063/31/2006 3:39:20 PMPFAIL
Phone line troubles and induct detectors did not report correctly. Need to reverify all zones.
BLD05-02966 FIRE-Final Inspection3/30/20063/31/20063/31/2006 3:38:14 PMPPASS
life safety finaled
FIR05-00884 INSP-Final Inspection3/30/20063/31/20063/31/2006 3:37:46 PMPPASS
Permit finaled
FIR05-00860 INSP-Final Inspection3/30/20063/31/20063/31/2006 3:37:31 PMPPASS
Permit finaled
FIR06-00076 INSP-Final Inspection3/31/20063/31/20063/31/2006 3:37:14 PMPPASS
Permit finaled
FIR05-00596 INSP-Supply line flush3/31/20063/31/20063/31/2006 2:26:50 PMPPASS
underground flush passed
FIR05-00509 INSP-Sprinkler Rough-in/Hydro3/31/20063/31/20063/31/2006 2:25:18 PMPPASS
Underground hydro test and flush passed.
BLD04-03001 FIRE-Final Inspection3/31/20063/31/20063/31/2006 12:53:03 PMPPASS
Life safety finaled.
FIR05-00644 INSP-Supply line flush3/30/20063/31/20063/31/2006 12:37:31 PMAFAIL
Wrong permit number called in. See FIR05-00509 for entry.
FIR05-00644 INSP-Sprinkler Rough-in/Hydro3/30/20063/31/20063/31/2006 12:37:10 PMAFAIL
Wrong permit number called in. See FIR05-00509 for entry.
FIR06-00164 INSP-Sprinkler Rough-in3/30/20063/31/20063/31/2006 11:09:55 AMAPASS
Sprinkler piping above the hard lid areas is ok to cover
BLD06-00144 FIRE-Final Inspection3/30/20063/31/20063/31/2006 10:48:03 AMAPASS
Life safety finaled. Second fire extinguisher is not required but owner said it would be installed anyway when they purchase the mounting bracket.
BLD06-00052 FIRE-Final Inspection3/30/20063/31/20063/31/2006 10:31:48 AMAPASS
life safety finaled. Fire extinguisher contractor is on their way to install the fire extinguisher on the mezzanine level.
BLD05-00087 FIRE-Final Inspection3/30/20063/31/20063/31/2006 10:05:57 AMACANC
to be rescheduled
BLD05-03423 FIRE-Final Inspection3/30/20063/31/20063/31/2006 9:34:15 AMAFAIL
Provide approved door hardware on the office doors.
BLD04-02937 FIRE-Final Inspection3/29/20063/31/20063/31/2006 9:16:24 AMAFAIL
Sprinkler heads need to be added in the large storage room due to a ceiling being added. Also separations have been added around the riser room that may affect sprinkler coverage.
FIR05-00487 INSP-Alarm Testing3/29/20063/31/20063/31/2006 9:11:23 AMAPASS
permit finaled
BLD05-02818 FIRE-Final Inspection3/30/20063/31/20063/31/2006 8:21:20 AMAPASS
Life safety finaled. Fire extinguisher contractor is on the way to tag the fire extinguisher.
BLD05-02817 FIRE-Final Inspection3/30/20063/31/20063/31/2006 8:20:29 AMAPASS
Life safety finaled.
FIR06-00177 INSP-Final Inspection3/31/20063/31/20063/31/2006 8:05:34 AMPPASS
permit finaled
FIR05-00594 INSP-Sprinkler Rough-in3/30/20063/31/20063/31/2006 7:52:19 AMAPASS
sprinkler piping in the lower ceilings on the first floor are ok to cover. See city approved plans for locations . The west side lower ceiling has a lower soffit that will require an additional sprinkler head to provide proper coverage. Also marked on plans.
BLD05-01577 FIRE-Final Inspection3/30/20063/31/20063/30/2006 2:56:51 PMAPASS
Life safety finaled
FIR06-00138 INSP-Final Inspection3/29/20063/31/20063/30/2006 12:34:37 PMAFAIL
Duplicate inspection from yesterday. Need to re-install the sprig up along the west exterior wall that was removed and install ceiling tile.