Inspections for the day of: Tuesday, March 31, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00492 Final3/31/20093/31/20093/31/2009 3:59:44 PMPPASS
Shane Phone #: ###-####
ELE08-01115 Final3/31/20093/31/20093/31/2009 3:26:27 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS
install required receps above counter by kitchen sink install proper sized boxes at built in glass shelves and the other sicde of that wall. GFCI protect receps within 6 ft of sink in mud room flex not permited with nm boxes by kitchen sink means of support to be external on nm boxes
ESC07-00904 General Inspection3/31/20093/31/20093/31/2009 1:38:58 PMPPASS
looks ok
ELE09-00517 Electrical Rough-In3/31/20093/31/20093/31/2009 1:36:46 PMPPART
Jim Phone #: ###-####
underground ok no esc in project
ELE09-00522 Electrical Rough-In3/31/20093/31/20093/31/2009 12:53:09 PMPPASS
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten
ELE09-00522 DOC - Permit Finaled3/31/20093/31/20093/31/2009 12:51:49 PMPPASS
ELE08-00373 Electrical Rough-In3/30/20093/31/20093/31/2009 11:49:19 AMAPART
john Phone #: ###-####
anop
ELE09-00513 Temporary Service3/30/20093/31/20093/31/2009 10:04:52 AMAFAIL
Overhead pole on west side of property, below main power pole feeding residence. Phone #: ###-#### Internet Inspection Request from: Therrin Robertson
no means to use power
ELE08-02803 Permanent Service3/30/20093/31/20093/31/2009 9:47:25 AMAPART
alan Phone #: ###-####
had conf about grounding and bonding
ELE09-00421 Final3/30/20093/31/20093/31/2009 9:03:01 AMACANC
Please provide final inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
not ready
ELE09-00512 Electrical Rough-In3/30/20093/31/20093/31/2009 9:01:04 AMAPASS
early as possible//Chris ###-####