FIR07-00745
| INSP-Conference | 3/26/2009 | 3/27/2009 | | P | |
|
|
Inspection follow up.
|
FIR08-00607
| INSP-Alarm Testing | 3/30/2009 | 3/31/2009 | 3/31/2009 5:45:50 PM | A | CANC |
|
|
Cnceled due to time constraints
|
BLD08-01467
| FIRE-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 2:16:42 PM | A | CANC |
|
|
Could not perform inspection due to time constraints.
|
FIR09-00030
| INSP-Supply line flush | 3/31/2009 | 3/31/2009 | 3/31/2009 2:10:37 PM | P | PASS |
|
|
The underground flush passed.
|
FIR09-00030
| INSP-Sprinkler Rough-in/Hydro | 3/31/2009 | 3/31/2009 | 3/31/2009 2:09:08 PM | P | PASS |
|
|
The underground hydro test passed.
|
FIR06-00469
| INSP-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 1:47:52 PM | A | FAIL |
|
|
There are three pendant heads blocked by obstructions. One is by a hanging light in the first floor north dining area. THe other two are too close to ceiling fans in the second floor bedrooms. Also the wrong sized water meeter was not addressed with the last resubmittals and does need to be addressed with resubmittals. The water meter currently installed is 1" in size. I spoke to Mick about these items.
|
BLD08-01664
| FIRE-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 1:20:03 PM | A | FAIL |
|
|
The project related fire alarm permit needs to be finaled prior to this inspection. A preliminary inspection was previously provided.
|
FIR09-00130
| INSP-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 1:19:02 PM | A | FAIL |
|
|
Need a map showing the entire system at the facp, repair the NAC trouble, test/inspect the elevator recall functions and per IFC 904.3.5 the clean agent suppression system is required to be monitored. See Monitoring. Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72.
|
FIR08-00778
| INSP-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 1:14:37 PM | A | PASS |
|
|
Permit finaled
|
FIR09-00061
| INSP-Alarm Testing | 3/30/2009 | 3/31/2009 | 3/31/2009 9:55:21 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 3/30/2009 at 3:21:50 PM. Contact: ###-####.
|
FIR09-00123
| INSP-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 9:54:52 AM | A | PASS |
|
|
permit finaled
|
BLD09-00380
| FIRE-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 9:44:23 AM | A | FAIL |
|
|
Steve French ###-#### I left a voice message on the answering machine. There was also no one on site or access into the suite.
|
FIR08-00824
| INSP-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 9:37:26 AM | A | PASS |
|
|
pemit finaled
|
FIR09-00136
| INSP-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 9:36:32 AM | A | PASS |
|
|
Permit finaled
|
BLD09-00062
| FIRE-Final Inspection | 3/30/2009 | 3/31/2009 | 3/31/2009 8:53:28 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Darren Gossett Inspection cancelled from web by: Darren Gossett
|