Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF16-00022 INSP-Final3/31/20163/31/20163/31/2016 2:31:57 PMPPASS
Previously noted items addressed/repaired. No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Fianl life fire safety inspection passed/complete.
NAF15-00042 INSP-Sprinkler Rough-in3/30/20163/31/20163/31/2016 11:25:14 AMAPASS
Rough to cover inspection complete for underground supply main, underground approved for cover.
FIR16-00093 INSP-Sprinkler Rough-in/Hydro3/30/20163/31/20163/31/2016 10:55:03 AMAPASS
Underground hydrostatic test complete, underground rough to cover inspection passed/complete, underground approved for cover.
BLD15-01520 FIRE-Final Inspection3/31/20163/31/20163/31/2016 10:34:50 AMPPASS
Previously noted items addressed/repaired. Final life fire safety inspection passed/complete
BLD15-04344 FIRE-Final Inspection3/30/20163/31/20163/31/2016 10:19:07 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers have current inspections tags and are in place. Final life fire safety inspection passed/complete
FIR16-00077 INSP-Final Inspection3/30/20163/31/20163/31/2016 10:17:03 AMAPASS
Final fire sprinkler inspection passed/complete
BLD15-04191 FIRE-Conference3/30/20163/31/20163/31/2016 9:15:52 AMADONE
Fire conference complete
BLD16-00709 FIRE-Final Inspection3/30/20163/31/20163/31/2016 8:29:30 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher has current inspection tag, discussed with tenant a suitable location for fire extinguisher mounting to wall. Final life fire safety inspection passed/complete.
BLD15-01520 FIRE-Final Inspection3/30/20163/31/20163/31/2016 7:54:14 AMAFAIL
Emergency egress light in the corridor was not attached to wall with wires visible, fire extinguishers need to have an inspection performed by a lisenced contractor and a current inspection tag needs to be attached. Audio/visual device on fire alarm system not attached to finished ceiling. Items need to be addressed beofre next inspection.