ELE02-00492
| Rough-In Permanent Service | 3/1/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 03/01/2002 at 08:31:41. Contact: ###-####. r/i ok, not service at this time, left message with contractor to discuss service installation. 3/4/2002 11:04:28 AM
|
ELE01-03860
| Permanent Service | 3/1/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | A | FAIL |
|
|
###-#### BILL KEY AT BOTTOM OF MAIN DISCONNECT nec: 250. equiptment bonding required. 110-26: clearances in front of disconnect. lock-nuts not approved for damp locations. discussed violations with contractor. idaho power connected to power before inspection.. 3/4/2002 11:02:29 AM
|
ELE01-03858
| Permanent Service | 3/1/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | A | FAIL |
|
|
###-#### BILL KEY AT BOTTOM OF MAIN DISCONNECT nec: 250. equiptment bonding, lock-nuts not approved for damp locations ufer ground chokes 110-26: cleareances in front of disconnect. discussed violations with contractor. idaho power connected to power before inspection. 3/4/2002 10:59:28 AM
|
ELE01-04024
| Final | 3/1/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | A | PASS |
|
|
###-#### RON
|
ELE02-00457
| Electrical Rough-In | 3/3/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 03/03/2002 at 20:02:18. Contact: ###-####. c 3/4/2002 10:47:54 AM m 3/4/2002 10:47:56 AM
|
ELE02-00475
| Rough-In Permanent Service | 3/4/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | P | PART |
|
|
r/i & ser -###-####- marv. only r/i, garage in back 3/4/2002 3:41:16 PM
|
ELE01-03703
| Rough-In Permanent Service | 3/4/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | P | PASS |
|
|
###-#### ROY . ele r/i; perm/svc.
p/s ug re roy kay ele #3703-ok 3/4/2002 4:12:30 PM
|
ELE02-00136
| Electrical Rough-In | 3/4/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | P | PASS |
|
|
kevin ###-#### r/i. upstairs over garage r/i. 3/4/2002 3:06:52 PM
|
ELE02-00525
| Rough-In Permanent Service | 3/4/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | P | PASS |
|
|
###-#### ALAN. r/i; perm/svc.
p/s ug new bullit ele #0525-ok 3/4/2002 2:32:52 PM
|
ELE02-00167
| Final | 3/1/2002 | 3/4/2002 | 3/4/2002 12:00:00 AM | P | PART |
|
|
###-####. temporary occupancy, pharmacy area only. 3/4/2002 4:44:47 PM
|