Inspections for the day of: Monday, March 4, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-00492 Rough-In Permanent Service3/1/20023/4/20023/4/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 03/01/2002 at 08:31:41. Contact: ###-####. r/i ok, not service at this time, left message with contractor to discuss service installation. 3/4/2002 11:04:28 AM
ELE01-03860 Permanent Service3/1/20023/4/20023/4/2002 12:00:00 AMAFAIL
###-#### BILL KEY AT BOTTOM OF MAIN DISCONNECT nec: 250. equiptment bonding required. 110-26: clearances in front of disconnect. lock-nuts not approved for damp locations. discussed violations with contractor. idaho power connected to power before inspection.. 3/4/2002 11:02:29 AM
ELE01-03858 Permanent Service3/1/20023/4/20023/4/2002 12:00:00 AMAFAIL
###-#### BILL KEY AT BOTTOM OF MAIN DISCONNECT nec: 250. equiptment bonding, lock-nuts not approved for damp locations ufer ground chokes 110-26: cleareances in front of disconnect. discussed violations with contractor. idaho power connected to power before inspection. 3/4/2002 10:59:28 AM
ELE01-04024 Final3/1/20023/4/20023/4/2002 12:00:00 AMAPASS
###-#### RON
ELE02-00457 Electrical Rough-In3/3/20023/4/20023/4/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 03/03/2002 at 20:02:18. Contact: ###-####. c 3/4/2002 10:47:54 AM m 3/4/2002 10:47:56 AM
ELE02-00475 Rough-In Permanent Service3/4/20023/4/20023/4/2002 12:00:00 AMPPART
r/i & ser -###-####- marv. only r/i, garage in back 3/4/2002 3:41:16 PM
ELE01-03703 Rough-In Permanent Service3/4/20023/4/20023/4/2002 12:00:00 AMPPASS
###-#### ROY . ele r/i; perm/svc.

p/s ug re roy kay ele #3703-ok 3/4/2002 4:12:30 PM
ELE02-00136 Electrical Rough-In3/4/20023/4/20023/4/2002 12:00:00 AMPPASS
kevin ###-#### r/i. upstairs over garage r/i. 3/4/2002 3:06:52 PM
ELE02-00525 Rough-In Permanent Service3/4/20023/4/20023/4/2002 12:00:00 AMPPASS
###-#### ALAN. r/i; perm/svc.

p/s ug new bullit ele #0525-ok 3/4/2002 2:32:52 PM
ELE02-00167 Final3/1/20023/4/20023/4/2002 12:00:00 AMPPART
###-####. temporary occupancy, pharmacy area only. 3/4/2002 4:44:47 PM