Inspections for the day of: Thursday, March 4, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00745 INSP-Final Inspection3/3/20043/4/20043/4/2004 12:00:00 AMAFAIL
cantractor was not ready for inspection 3/4/2004 9:55:19 AM
FIR03-00295 INSP-Final Inspection3/3/20043/4/20043/4/2004 12:00:00 AMAFAIL
No approved plans on site and no access to inspect the fire sprinklers (ceiling tile has been installed) 3/4/2004 11:15:03 AM
FIR03-00713 INSP-Final Inspection3/3/20043/4/20043/4/2004 12:00:00 AMAFAIL
still need the backflow preventor friction loss verified since a different backflow preventor was installed. The flow switch did not activate the alarms (smoke detectors) 3/4/2004 8:46:20 AM
BLD02-02873 BLD-Conference3/4/20043/4/20043/4/2004 12:00:00 AMADONE
I went over life safety requirements in the remodeled area with store representative. They need to provide approved hardware on the mechanical room door. Remove key hardware on the aluminum glass door. Hang fire extinguishers that are sitting on the floor. Provide annual inspection for all fire extinguishers. Final sprinkler permit and test the emergency lights/exit signs in my presence.
FIR04-00014 INSP-Final Inspection3/1/20043/4/20043/4/2004 12:00:00 AMAPASS
hood suppression system operated correctly 3/4/2004 10:42:40 AM
FIR03-00730 INSP-Final Inspection3/2/20043/4/20043/4/2004 12:00:00 AMPPASS
fire alarm finaled 3/4/2004 3:51:52 PM
FIR03-00448 INSP-Sprinkler Rough-in/Hydro3/2/20043/4/20043/4/2004 12:00:00 AMPPART
Inspection was a hydro test. The hydro test passed but will need to be done again due to more sprinkler heads being cut into the piping as the project gets closer to completion 3/4/2004 3:44:08 PM
BLD03-01957 FIRE-Final Inspection3/4/20043/4/20043/4/2004 12:00:00 AMPPART
A temporary occupancy was given on the fire sprinkler permit with dave miller's permission until the backflow can be verified and the alarms work.
FIR03-00713 INSP-Final Inspection3/4/20043/4/20043/4/2004 12:00:00 AMPPART
A temporary occupancy was given with dave miller's permission until the backflow can be verified and the alarms work.
FIR03-00364 INSP-Final Inspection3/4/20043/4/20043/4/2004 12:00:00 AMPPASS
hood suppression system operated correctly
BLD03-02369 FIRE-Final Inspection3/4/20043/4/20043/4/2004 12:00:00 AMPPART
Phase 1 is ok to occupy 3/4/2004 2:25:11 PM