ELE04-03809
| ELE-Aging Inspection | 3/4/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | | PASS |
|
|
|
ELE05-00686
| Electrical Rough-In | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | PART |
|
|
###-#### - eric
except sitting room
box in recessed lights 3/4/2005 10:43:03 AM
|
ELE05-00644
| Temporary Service | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | NH |
|
|
Scheduled by a contractor via Hello! on 3/3/2005 at 11:33:35 AM. Contact: ###-####.
They waved me past I called to find out where to go and was told that they would find out and reschedual for mon. 3/4/2005 8:57:26 AM
|
ELE05-00694
| Temporary Service | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | FAIL |
|
|
karen ###-####
install guy kit nad GFCI protect temp receps. 3/4/2005 10:56:16 AM
|
ELE05-00694
| Temporary Service | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | FAIL |
|
|
karen ###-####
install guy kit nad GFCI protect temp receps. 3/4/2005 10:56:16 AM
|
ELE05-00509
| Electrical Rough-In | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | PART |
|
|
Please call 30min before for access. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer
termination incorrect
ok to cover 3/4/2005 9:39:11 AM
|
ELE05-00033
| Final | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | PASS |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
ELE05-00604
| Electrical Rough-In | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | PART |
|
|
8:30 am Stu; Phone #: ###-#### Internet Inspection Request from: Jan Rice 3/3/2005 3:10:04 PM
1 room on 5th floor 3/4/2005 9:40:31 AM
|
ELE05-00697
| Electrical Rough-In | 3/3/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | A | PASS |
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Jan Rice
kitchen remodel ok 3/4/2005 10:51:00 AM
|
ELE03-00099
| Electrical Rough-In | 3/4/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | P | FAIL |
|
|
peter; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
box fill.
screws in nm boxes.
6 in free conductor.
protection of romex.
staples within 8 in.
recep required upstairs.
wire terminations. 3/4/2005 2:03:10 PM
|
ELE05-00687
| Rough-In Permanent Service | 3/4/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/4/2005 at 8:38:35 AM. Contact: ###-####.
P/S O/H R OK 3/4/2005 2:21:36 PM
|
ELE05-00704
| Temporary Service | 3/4/2005 | 3/4/2005 | 3/4/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/4/2005 at 11:16:16 AM. Contact: ###-####.
check fault current.
raintingt enclouser for transformer
2/0 ground for parallel 500kcm
seal unused opening 3/4/2005 3:28:33 PM
|