Inspections for the day of: Friday, March 4, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03809 ELE-Aging Inspection3/4/20053/4/20053/4/2005 12:00:00 AM PASS
ELE05-00686 Electrical Rough-In3/3/20053/4/20053/4/2005 12:00:00 AMAPART
###-#### - eric
except sitting room
box in recessed lights 3/4/2005 10:43:03 AM
ELE05-00644 Temporary Service3/3/20053/4/20053/4/2005 12:00:00 AMANH
Scheduled by a contractor via Hello! on 3/3/2005 at 11:33:35 AM. Contact: ###-####.
They waved me past I called to find out where to go and was told that they would find out and reschedual for mon. 3/4/2005 8:57:26 AM
ELE05-00694 Temporary Service3/3/20053/4/20053/4/2005 12:00:00 AMAFAIL
karen ###-####
install guy kit nad GFCI protect temp receps. 3/4/2005 10:56:16 AM
ELE05-00694 Temporary Service3/3/20053/4/20053/4/2005 12:00:00 AMAFAIL
karen ###-####
install guy kit nad GFCI protect temp receps. 3/4/2005 10:56:16 AM
ELE05-00509 Electrical Rough-In3/3/20053/4/20053/4/2005 12:00:00 AMAPART
Please call 30min before for access. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer
termination incorrect
ok to cover 3/4/2005 9:39:11 AM
ELE05-00033 Final3/3/20053/4/20053/4/2005 12:00:00 AMAPASS
lloyd; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ELE05-00604 Electrical Rough-In3/3/20053/4/20053/4/2005 12:00:00 AMAPART
8:30 am Stu; Phone #: ###-#### Internet Inspection Request from: Jan Rice 3/3/2005 3:10:04 PM
1 room on 5th floor 3/4/2005 9:40:31 AM
ELE05-00697 Electrical Rough-In3/3/20053/4/20053/4/2005 12:00:00 AMAPASS
Terry; Phone #: ###-#### Internet Inspection Request from: Jan Rice
kitchen remodel ok 3/4/2005 10:51:00 AM
ELE03-00099 Electrical Rough-In3/4/20053/4/20053/4/2005 12:00:00 AMPFAIL
peter; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
box fill.
screws in nm boxes.
6 in free conductor.
protection of romex.
staples within 8 in.
recep required upstairs.
wire terminations. 3/4/2005 2:03:10 PM
ELE05-00687 Rough-In Permanent Service3/4/20053/4/20053/4/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/4/2005 at 8:38:35 AM. Contact: ###-####.
P/S O/H R OK 3/4/2005 2:21:36 PM
ELE05-00704 Temporary Service3/4/20053/4/20053/4/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 3/4/2005 at 11:16:16 AM. Contact: ###-####.
check fault current.
raintingt enclouser for transformer
2/0 ground for parallel 500kcm
seal unused opening 3/4/2005 3:28:33 PM