Inspections for the day of: Tuesday, March 4, 2008.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00606 INSP-Sprinkler Rough-in3/3/20083/4/20083/5/2008 2:56:40 PMPFAIL
See areas marked on approved plans for correction items including areas E and F first floor.
FIR08-00039 INSP-Sprinkler Rough-in/Hydro3/3/20083/4/20083/4/2008 6:58:13 PMAFAIL
Provide plan resubmittals reflecting field modifications and installation of CPVC piping for several branchlines.
FIR07-00997 INSP-Sprinkler Rough-in3/3/20083/4/20083/4/2008 6:55:52 PMPFAIL
Overspaced head at the restroom area, EC heads adjacent to the south and west walls of the sales floor area do not meet table 8.8.5.1.2 per NFPA 13 for clearance to ceiling mounted obstructions.
FIR07-00813 INSP-Final Inspection3/4/20083/4/20083/4/2008 6:47:06 PMAPASS
Fire sprinkler final inspection passed, missing calc. sticker at the riser to be provided as discussed.
FIR07-00813 INSP-Supply line flush3/4/20083/4/20083/4/2008 6:45:42 PMPPART
UG fire supply line flush completed satisfactory.
FIR07-00262 INSP-Final Inspection3/3/20083/4/20083/4/2008 3:40:05 PMAPASS
Fire alarm permit completed. KR
FIR07-00247 INSP-Final Inspection3/3/20083/4/20083/4/2008 2:54:27 PMAPASS
Fire alarm Permit finaled.KR
FIR07-00965 FIR-Aging Inspection3/4/20083/4/20083/4/2008 12:43:57 PM DEFR
Pending site inspection request when work is complete.
FIR07-00918 INSP-Final Inspection3/3/20083/4/20083/4/2008 12:41:49 PMAFAIL
Duct detector at one location failed to shut down the HVAC, new elevator recall programming per the building upgrade agreement tested satisfactory.
FIR07-01041 INSP-Sprinkler Rough-in/Hydro3/3/20083/4/20083/4/2008 12:31:29 PMAPART
Fire sprinkler system modifications are approved for cover at the drop ceiling areas only as circled and initialed on plans with todays date, some rooms are not yet completed for inspection at this time.
BLD07-02914 FIRE-Final Inspection3/3/20083/4/20083/4/2008 12:22:35 PMACANC
Life safety inspection cannot be completed until fire alarm permit FIR08-00129 is finaled.KR
BLD07-01428 FIRE-Final Inspection3/3/20083/4/20083/4/2008 12:20:39 PMAPASS
Correction items completed, life safety passed.
FIR07-00470 INSP-Final Inspection3/4/20083/4/20083/4/2008 12:15:21 PMAPASS
Fire alarm test complete.KR
FIR07-00469 INSP-Final Inspection3/4/20083/4/20083/4/2008 12:14:40 PMAPASS
Fire alarm test complete. KR
FIR08-00024 INSP-Final Inspection3/3/20083/4/20083/4/2008 11:15:30 AMAPASS
Fire alarm testing completed. KR
BLD07-03159 FIRE-Final Inspection3/3/20083/4/20083/4/2008 11:14:36 AMANR
Tucker; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
BLD07-03158 FIRE-Final Inspection3/3/20083/4/20083/4/2008 11:14:03 AMANR
Tucker; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
BLD07-03157 FIRE-Final Inspection3/3/20083/4/20083/4/2008 11:13:32 AMANR
FIR07-01037 INSP-Sprinkler Rough-in/Hydro2/28/20083/4/20082/28/2008 1:11:54 PMACANC
Forrest, Please call us when you know about when you can be out to this project, so we can notify the tenants. (Please also see FIR07-01038.) Thank You. ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick