FIR07-00606
| INSP-Sprinkler Rough-in | 3/3/2008 | 3/4/2008 | 3/5/2008 2:56:40 PM | P | FAIL |
|
|
See areas marked on approved plans for correction items including areas E and F first floor.
|
FIR08-00039
| INSP-Sprinkler Rough-in/Hydro | 3/3/2008 | 3/4/2008 | 3/4/2008 6:58:13 PM | A | FAIL |
|
|
Provide plan resubmittals reflecting field modifications and installation of CPVC piping for several branchlines.
|
FIR07-00997
| INSP-Sprinkler Rough-in | 3/3/2008 | 3/4/2008 | 3/4/2008 6:55:52 PM | P | FAIL |
|
|
Overspaced head at the restroom area, EC heads adjacent to the south and west walls of the sales floor area do not meet table 8.8.5.1.2 per NFPA 13 for clearance to ceiling mounted obstructions.
|
FIR07-00813
| INSP-Final Inspection | 3/4/2008 | 3/4/2008 | 3/4/2008 6:47:06 PM | A | PASS |
|
|
Fire sprinkler final inspection passed, missing calc. sticker at the riser to be provided as discussed.
|
FIR07-00813
| INSP-Supply line flush | 3/4/2008 | 3/4/2008 | 3/4/2008 6:45:42 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory.
|
FIR07-00262
| INSP-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 3:40:05 PM | A | PASS |
|
|
Fire alarm permit completed. KR
|
FIR07-00247
| INSP-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 2:54:27 PM | A | PASS |
|
|
Fire alarm Permit finaled.KR
|
FIR07-00965
| FIR-Aging Inspection | 3/4/2008 | 3/4/2008 | 3/4/2008 12:43:57 PM | | DEFR |
|
|
Pending site inspection request when work is complete.
|
FIR07-00918
| INSP-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 12:41:49 PM | A | FAIL |
|
|
Duct detector at one location failed to shut down the HVAC, new elevator recall programming per the building upgrade agreement tested satisfactory.
|
FIR07-01041
| INSP-Sprinkler Rough-in/Hydro | 3/3/2008 | 3/4/2008 | 3/4/2008 12:31:29 PM | A | PART |
|
|
Fire sprinkler system modifications are approved for cover at the drop ceiling areas only as circled and initialed on plans with todays date, some rooms are not yet completed for inspection at this time.
|
BLD07-02914
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 12:22:35 PM | A | CANC |
|
|
Life safety inspection cannot be completed until fire alarm permit FIR08-00129 is finaled.KR
|
BLD07-01428
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 12:20:39 PM | A | PASS |
|
|
Correction items completed, life safety passed.
|
FIR07-00470
| INSP-Final Inspection | 3/4/2008 | 3/4/2008 | 3/4/2008 12:15:21 PM | A | PASS |
|
|
Fire alarm test complete.KR
|
FIR07-00469
| INSP-Final Inspection | 3/4/2008 | 3/4/2008 | 3/4/2008 12:14:40 PM | A | PASS |
|
|
Fire alarm test complete. KR
|
FIR08-00024
| INSP-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 11:15:30 AM | A | PASS |
|
|
Fire alarm testing completed. KR
|
BLD07-03159
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 11:14:36 AM | A | NR |
|
|
Tucker; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
BLD07-03158
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 11:14:03 AM | A | NR |
|
|
Tucker; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
BLD07-03157
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 11:13:32 AM | A | NR |
|
|
|
FIR07-01037
| INSP-Sprinkler Rough-in/Hydro | 2/28/2008 | 3/4/2008 | 2/28/2008 1:11:54 PM | A | CANC |
|
|
Forrest, Please call us when you know about when you can be out to this project, so we can notify the tenants. (Please also see FIR07-01038.) Thank You. ###-#### Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|