MIS07-00153
| FIR-Conference | 2/26/2008 | 3/4/2008 | 3/5/2008 4:28:11 PM | P | DONE |
|
|
Per Darren almost all of the items required for the racking permit have been gathered and he will be submitting to the city soon. A follow up inspection for next week has been scheduled.
|
BLD05-03423
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 3:50:57 PM | P | PASS |
|
|
Life safety passed. Structural inspector to verify that the deadbolt lock is removed from the common restroom door as per the approved drawings.
|
BLD05-03391
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 3:33:26 PM | P | FAIL |
|
|
The upper level life safety is passed. The lower level is failed. There are missing exit discharge lights, emergency lights and exit signs.
|
BLD07-02654
| FIRE-Final Inspection | 3/4/2008 | 3/4/2008 | 3/4/2008 2:48:39 PM | P | FAIL |
|
|
Repair the exit sign, tag the fire extinguishers and remove the dead bolt off of the office door.
|
BLD07-01506
| FIRE-Conference | 3/3/2008 | 3/4/2008 | 3/4/2008 2:46:09 PM | A | FAIL |
|
|
Provide address facing overland and the side street as discussed. Remove the short sample tubes in the duct smoke detectors and relocate the long tube to the lower position. Also provide the correct remote annunciators and test the duct smoke detectors.
|
FIR07-00745
| FIR-Aging Inspection | 3/4/2008 | 3/4/2008 | 3/4/2008 12:36:31 PM | | NR |
|
|
I left message on the contractors voice mail requesting status of project.
|
BLD08-00314
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 12:07:22 PM | A | PASS |
|
|
life safety passed
|
BLD07-02976
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 12:06:50 PM | A | PASS |
|
|
life safety passed
|
BLD07-02975
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 12:05:49 PM | A | PASS |
|
|
life safety passed
|
FIR07-01037
| INSP-Final Inspection | 2/28/2008 | 3/4/2008 | 3/4/2008 12:04:27 PM | A | PASS |
|
|
Permit finaled
|
FIR07-01038
| INSP-Final Inspection | 2/28/2008 | 3/4/2008 | 3/4/2008 12:03:46 PM | A | PASS |
|
|
Permit finaled
|
BLD07-02654
| FIRE-Alarm Testing | 3/4/2008 | 3/4/2008 | 3/4/2008 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 3/4/2008 at 6:37:56 AM. Contact: ###-####.
|
BLD07-03143
| FIRE-Final Inspection | 3/3/2008 | 3/4/2008 | 3/4/2008 12:00:00 AM | P | CANC |
|
|
Duane, early afternoon if possible, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|