Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS07-00153 FIR-Conference2/26/20083/4/20083/5/2008 4:28:11 PMPDONE
Per Darren almost all of the items required for the racking permit have been gathered and he will be submitting to the city soon. A follow up inspection for next week has been scheduled.
BLD05-03423 FIRE-Final Inspection3/3/20083/4/20083/4/2008 3:50:57 PMPPASS
Life safety passed. Structural inspector to verify that the deadbolt lock is removed from the common restroom door as per the approved drawings.
BLD05-03391 FIRE-Final Inspection3/3/20083/4/20083/4/2008 3:33:26 PMPFAIL
The upper level life safety is passed. The lower level is failed. There are missing exit discharge lights, emergency lights and exit signs.
BLD07-02654 FIRE-Final Inspection3/4/20083/4/20083/4/2008 2:48:39 PMPFAIL
Repair the exit sign, tag the fire extinguishers and remove the dead bolt off of the office door.
BLD07-01506 FIRE-Conference3/3/20083/4/20083/4/2008 2:46:09 PMAFAIL
Provide address facing overland and the side street as discussed. Remove the short sample tubes in the duct smoke detectors and relocate the long tube to the lower position. Also provide the correct remote annunciators and test the duct smoke detectors.
FIR07-00745 FIR-Aging Inspection3/4/20083/4/20083/4/2008 12:36:31 PM NR
I left message on the contractors voice mail requesting status of project.
BLD08-00314 FIRE-Final Inspection3/3/20083/4/20083/4/2008 12:07:22 PMAPASS
life safety passed
BLD07-02976 FIRE-Final Inspection3/3/20083/4/20083/4/2008 12:06:50 PMAPASS
life safety passed
BLD07-02975 FIRE-Final Inspection3/3/20083/4/20083/4/2008 12:05:49 PMAPASS
life safety passed
FIR07-01037 INSP-Final Inspection2/28/20083/4/20083/4/2008 12:04:27 PMAPASS
Permit finaled
FIR07-01038 INSP-Final Inspection2/28/20083/4/20083/4/2008 12:03:46 PMAPASS
Permit finaled
BLD07-02654 FIRE-Alarm Testing3/4/20083/4/20083/4/2008 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 3/4/2008 at 6:37:56 AM. Contact: ###-####.
BLD07-03143 FIRE-Final Inspection3/3/20083/4/20083/4/2008 12:00:00 AMPCANC
Duane, early afternoon if possible, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt